Main Functions
SiBE041401E
21
Function and Control
1.6
Program Dry Operation
Outline
Program dry operation removes humidity while preventing the room temperature from lowering.
Since the microcomputer controls both the temperature and airflow rate, the temperature
adjustment and
FAN
setting buttons are inoperable.
Detail
The microcomputer automatically sets the temperature and airflow rate. The difference between
the room thermistor temperature at start-up and the target temperature is divided into two
zones. Then, the unit operates in an appropriate capacity for each zone to maintain the
temperature and humidity at a comfortable level.
Room thermistor
temperature at start-up
Target temperature
X
Thermostat OFF point
Y
Thermostat ON point
Z
24ºC or more
Room thermistor
temperature at start-up
X
–
2.0ºC
X
–
0.5ºC
or
Y + 0.5ºC (zone B)
continues for 10 min.
23.5ºC
X
–
1.5ºC
X
–
0.5ºC
or
Y + 0.5ºC (zone B)
continues for 10 min.
~
18ºC
18ºC
X
–
1.5ºC
X
–
0.5ºC = 17.5ºC
or
Y + 0.5ºC (zone B)
continues for 10 min.
17.5ºC
~
Zone A = Thermostat OFF
Y
+0.5ºC
Z
X
Zone B
Zone B
Zone C = Thermostat ON
(R11581)
Summary of Contents for FTXG20LV1BW
Page 12: ...SiBE041401E 1 List of Functions Part 1 List of Functions 1 Functions 2...
Page 14: ...SiBE041401E 3 Specifications Part 2 Specifications 1 Specifications 4...
Page 60: ...SiBE041401E 49 Remote Controller Part 5 Remote Controller 1 Remote controller 50...
Page 113: ...SiBE041401E Check Service Diagnosis 102 50 class Diode bridge R19944...
Page 127: ...Revision History Month Year Version Revised contents 03 2014 SiBE041401E First edition...