SiBE041401E
Tips for Servicing
Trial Operation and Field Settings
104
1. Tips for Servicing
1.1
Pump Down Operation
Outline
In order to protect the environment, be sure to conduct pump down operation when relocating or
disposing of the unit.
Detail
1) Remove the valve caps from the liquid stop valve and the gas stop valve.
2) Carry out forced cooling operation.
3) After 5 to 10 minutes, close the liquid stop valve with a hexagonal wrench.
4) After 2 to 3 minutes, close the gas stop valve and stop the forced cooling operation.
Refer to forced cooling operation below.
1.2
Forced Cooling Operation
Gas stop valve
Valve cap
Close
Liquid stop valve
Service port
(R13628)
Hexagonal
wrench
Item
Forced Cooling
Conditions
The forced cooling operation is allowed when both of the following conditions are
met.
1) The outdoor unit is not abnormal and not in the 3-minute standby mode.
2) The outdoor unit is not operating.
Start
The forced cooling operation starts when any of the following conditions are fulfilled.
1) Press the forced cooling operation
ON/OFF
button (S1W) on the indoor unit for 5
seconds.
2) Press the forced cooling operation ON/OFF button (SW1) on the outdoor unit
within around 3 minutes after power is supplied with standby electricity saving
function turned off.
Command
frequency
20/25/35 class: 58 Hz
50 class: 66 Hz
End
The forced cooling operation ends when any of the following conditions are fulfilled.
1) The operation ends automatically after 15 minutes.
2) Press the forced cooling operation
ON/OFF
button (S1W) on the indoor unit again.
3) Press the
ON/OFF
button on the remote controller.
4) Press the forced cooling operation ON/OFF button (SW1) on the outdoor unit.
Others
Protection functions have priority over all other functions during forced cooling
operation.
Summary of Contents for FTXG20LV1BW
Page 12: ...SiBE041401E 1 List of Functions Part 1 List of Functions 1 Functions 2...
Page 14: ...SiBE041401E 3 Specifications Part 2 Specifications 1 Specifications 4...
Page 60: ...SiBE041401E 49 Remote Controller Part 5 Remote Controller 1 Remote controller 50...
Page 113: ...SiBE041401E Check Service Diagnosis 102 50 class Diode bridge R19944...
Page 127: ...Revision History Month Year Version Revised contents 03 2014 SiBE041401E First edition...