Functions of Cooling Only Models
Si01-406
28
Functions and Control
1.12
Auto-restart Function
If there is a power cut when the unit is operating, it will automatically resume the same operating
mode when the power is restored.
Note:
It takes 3 minutes to restart the operation because the 3-minute standby function is activated.
Store Data
Power ON/OFF
Operation mode
Set temperature
Fan operation mode
Swing ON/OFF
Flap angle
ON/OFF Timer
1.13
Test Run Function
A compressor test run can be made regardless of room temperature and without turning the
compressor ON-OFF from the thermistor.
The compressor can be turned ON for 15 minutes in either the cool or dry mode, even though
the compressor is OFF on the thermostat. This is done by setting the test mode from the remote
controller.
After trial operation is complete, set the temperature to a normal level (26°C to 28°C).
For protection, the machine disables restart operation for 3 minutes after it is turned off.
Trial operation from Remote Controller
(1)
Press ON/OFF button to turn on the system.
(2)
Simultaneously press DOWN, UP, and MODE buttons.
(3)
Press MODE button twice.
(“
T
” will appear on the display to indicate that Trial Operation mode is selected.)
(4)
Trial run mode terminates in approx. 30 minutes and switches into normal mode. To quit a trial
operation, press ON/OFF button.
15 min.
5 sec.
ON
Indoor Unit
ON/OFF
switch
Compressor
Indoor fan
OFF
ON
OFF
SET
OFF
(R3094)