Check
Si01-406
118
Service Diagnosis
5.5
Discharge Pressure Check
Check No.8
Discharge pressure check
Replace compessor.
Open the stop valve.
Replace the pipe installed at
the site.
Clean.
Replace the compressor.
(R3049)
Not dirty
YES
YES
Dirty
NO
NO
NO
Are the heat exchanger and
air filter dirty?
Is the stop valve open?
Is the
connection pipe deformed?
YES
High