ESIE02–01
Error Codes: Indoor Units
Part 3 – Troubleshooting
3–27
4
5
1
3
2.5
Malfunctioning Drain System (
AF
)
Error code
AF
LED indications
The table below shows the LED indications.
Error generation
The error is generated when the float switch changes from ON to OFF while the compressor is OFF.
Causes
The possible causes are:
■
Error in the drain pipe installation
■
Malfunctioning float switch
■
Malfunctioning indoor unit PCB.
Troubleshooting
To troubleshoot, proceed as follows:
Operation
HAP (green)
HBP (green)
Normal
6
6
Malfunctioning
6
6
Are float
switch and drain pipe
normal?
Is water
drainage system
normal?
Possible failure of float switch.
Check to see if drain-up height
and horizontal pipe length
exceed specifications.
Clogged drain water discharge
system
Clogged drain pump
Faulty float switch
Replace indoor unit PCB.
Check to see if drain-up height
and horizontal pipe length
exceed specifications.
Check jumper connector
X15A.
Check drain pump and drain
pipe.
Check water drainage system.
Check to see if drain-up height
and horizontal pipe length
exceed specifications.
Faulty trap in water drainage
system
Replace indoor unit PCB.
Is drain-up
kit installed?
Is drain pump
normal?
Is
amount
of circulated drain
water excessive after
pump stops
operation?
Does
drain water
flow in reverse during
non-operation?
∗
In FHY and FAY problems can also
occur in the optional drain-up kit.
NO
YES
YES
YES
YES
YES
YES
NO
NO
NO
NO
NO
Summary of Contents for FHC45BZ7V1
Page 1: ...ESIE02 01 Service Manual Sky Air R 407C B series SV p p p...
Page 2: ......
Page 3: ...ESIE02 01 Service Manual Sky Air R 407C B series SV p p p...
Page 4: ......
Page 16: ...Introduction ESIE02 01 xii 3 1 4 5...
Page 18: ...ESIE02 01 1 2 Part 1 System Outline 3 1 1 5...
Page 42: ...General Outline Outdoor Units ESIE02 01 1 26 Part 1 System Outline 3 1 1 4 5...
Page 49: ...ESIE02 01 General Outline Indoor Units Part 1 System Outline 1 33 3 1 4 5...
Page 72: ...General Outline Indoor Units ESIE02 01 1 56 Part 1 System Outline 3 1 1 4 5...
Page 86: ...Specifications ESIE02 01 1 70 Part 1 System Outline 3 1 1 4 5...
Page 110: ...ESIE02 01 1 94 Part 1 System Outline...
Page 130: ...Switch Box Layout ESIE02 01 1 114 Part 1 System Outline 3 1 1 4 5...
Page 180: ...PCB Layout ESIE02 01 1 164 Part 1 System Outline 3 1 1 4 5...
Page 182: ...ESIE02 01 2 2 Part 2 Functional Description 3 1 2 5...
Page 204: ...General Functionality ESIE02 01 2 24 Part 2 Functional Description 3 1 2 4 5...
Page 216: ...Overview of the cooling mode functions ESIE02 01 2 36 Part 2 Functional Description 3 1 2 4 5...
Page 232: ...ESIE02 01 3 2 Part 3 Troubleshooting 3 1 3 5...
Page 294: ...Error Codes System Malfunctions ESIE02 01 3 64 Part 3 Troubleshooting 3 1 3 4 5...