General Functionality
ESIE02–01
2–8
Part 2 – Functional Description
3
1
2
4
5
1.5
Forced Operating Mode (Emergency Operation)
Applicable units
The forced operating mode is applicable for the following units:
Purpose
The table below describes the purpose of the forced operating mode.
Starting conditions
You can operate the system manually by changing the emergency switch on the indoor and outdoor
PCB from “normal” to “emergency”. However, when in emergency operation, the equipment cannot
control the temperature.
Make sure to set both indoor and outdoor unit to emergency. See page 2–10.
Ending conditions
You can end the emergency operation by changing the emergency switch back to “normal” while the
power is OFF.
Emergency
operation
The table below describes what happens when you change the emergency switch to “emergency”.
Model type
For this unit, you can go to...
RY35-45E(A)Z7V1
■
Forced cooling mode
■
Capacity control
RP71-250B
Forced cooling mode
RYP71-250B
■
Forced cooling mode
■
Forced heating mode
If...
Then...
■
Remocon is malfunctioning, or
■
Indoor PCB is off line, or
■
Outdoor PCB is off line
Forced operating mode can be used to go to cooling or heat-
ing. In forced operating mode, the compressor is forced to
operate until the malfunctioning indoor or outdoor PCB is
back online.
Changing the emergency switch to
“emergency” for the...
Switches ON...
Indoor unit
■
Indoor fan
■
Drain pump
Outdoor unit
■
Compressor
■
Outdoor fan(s)
Summary of Contents for FHC45BZ7V1
Page 1: ...ESIE02 01 Service Manual Sky Air R 407C B series SV p p p...
Page 2: ......
Page 3: ...ESIE02 01 Service Manual Sky Air R 407C B series SV p p p...
Page 4: ......
Page 16: ...Introduction ESIE02 01 xii 3 1 4 5...
Page 18: ...ESIE02 01 1 2 Part 1 System Outline 3 1 1 5...
Page 42: ...General Outline Outdoor Units ESIE02 01 1 26 Part 1 System Outline 3 1 1 4 5...
Page 49: ...ESIE02 01 General Outline Indoor Units Part 1 System Outline 1 33 3 1 4 5...
Page 72: ...General Outline Indoor Units ESIE02 01 1 56 Part 1 System Outline 3 1 1 4 5...
Page 86: ...Specifications ESIE02 01 1 70 Part 1 System Outline 3 1 1 4 5...
Page 110: ...ESIE02 01 1 94 Part 1 System Outline...
Page 130: ...Switch Box Layout ESIE02 01 1 114 Part 1 System Outline 3 1 1 4 5...
Page 180: ...PCB Layout ESIE02 01 1 164 Part 1 System Outline 3 1 1 4 5...
Page 182: ...ESIE02 01 2 2 Part 2 Functional Description 3 1 2 5...
Page 204: ...General Functionality ESIE02 01 2 24 Part 2 Functional Description 3 1 2 4 5...
Page 216: ...Overview of the cooling mode functions ESIE02 01 2 36 Part 2 Functional Description 3 1 2 4 5...
Page 232: ...ESIE02 01 3 2 Part 3 Troubleshooting 3 1 3 5...
Page 294: ...Error Codes System Malfunctions ESIE02 01 3 64 Part 3 Troubleshooting 3 1 3 4 5...