ESIE02–01
General Functionality
Part 2 – Functional Description
2–23
3
2
4
5
1
1.17
Using Conditions for Remote Control Thermostat
Applicable units
All units
Wired remote
controls
The remote control thermostat is only available in wired remote controls.
Conditions in which
the rem. contr.
thermostat is not
used
Even when the “use remote control thermostat” is selected in service mode, the remote control
thermostat is not always used.
The table below contains the conditions in which the remote control thermostat is not used.
Cooling
The diagram below shows the operation range of the set temperature/air suction temperature
combination.
Heating
The diagram below shows the operation range of the set temperature/air suction temperature
combination.
Condition
The remote control thermostat is not
used when...
Except...
1
The remote control thermostat malfunctions.
—
2
The “one remote control group control” is
selected.
For simultaneous ON/OFF operation.
3
The set temp./air suction temp. combination
is out of range. See further in this section.
When the automatic operation is
selected. If so, the remote control
can be used.
Remote control thermostat
operation range
Differential zone
th: Suction air temp.
(˚C)
ts: Set temp.
(˚C)
Remote control thermostat
operation range
Differential zone
th: Suction air temp.
(˚C)
ts: Set temp.
(˚C)
Summary of Contents for FHC45BZ7V1
Page 1: ...ESIE02 01 Service Manual Sky Air R 407C B series SV p p p...
Page 2: ......
Page 3: ...ESIE02 01 Service Manual Sky Air R 407C B series SV p p p...
Page 4: ......
Page 16: ...Introduction ESIE02 01 xii 3 1 4 5...
Page 18: ...ESIE02 01 1 2 Part 1 System Outline 3 1 1 5...
Page 42: ...General Outline Outdoor Units ESIE02 01 1 26 Part 1 System Outline 3 1 1 4 5...
Page 49: ...ESIE02 01 General Outline Indoor Units Part 1 System Outline 1 33 3 1 4 5...
Page 72: ...General Outline Indoor Units ESIE02 01 1 56 Part 1 System Outline 3 1 1 4 5...
Page 86: ...Specifications ESIE02 01 1 70 Part 1 System Outline 3 1 1 4 5...
Page 110: ...ESIE02 01 1 94 Part 1 System Outline...
Page 130: ...Switch Box Layout ESIE02 01 1 114 Part 1 System Outline 3 1 1 4 5...
Page 180: ...PCB Layout ESIE02 01 1 164 Part 1 System Outline 3 1 1 4 5...
Page 182: ...ESIE02 01 2 2 Part 2 Functional Description 3 1 2 5...
Page 204: ...General Functionality ESIE02 01 2 24 Part 2 Functional Description 3 1 2 4 5...
Page 216: ...Overview of the cooling mode functions ESIE02 01 2 36 Part 2 Functional Description 3 1 2 4 5...
Page 232: ...ESIE02 01 3 2 Part 3 Troubleshooting 3 1 3 5...
Page 294: ...Error Codes System Malfunctions ESIE02 01 3 64 Part 3 Troubleshooting 3 1 3 4 5...