General Functionality
ESIE02–01
2–16
Part 2 – Functional Description
3
1
2
4
5
1.11
Discharge Pipe Temperature Control
Applicable units
R(Y)P71-250B
Purpose
The purpose of the discharge pipe temperature control is to prevent a discharge pipe temperature that
is too high or too low.
Low temp.
starting conditions
The table below contains the low temperature conditions to start the discharge pipe temperature
control.
High temp.
starting conditions
The table below contains the high temperature conditions to start the discharge pipe temperature
control.
Used input
The discharge pipe temperature control uses the following inputs:
Function
Description
Starting conditions
F3-error occurs if
the conditions...
Wet operation
Prevents liquid suction to
the compressor.
■
Change in E.V. opening
< 50 pulses
■
Td < Tc + 10˚C
Are met for 15 min
continuously.
Thermistor
out
Detects if the discharge
thermistor is not in the cor-
rect position.
■
Td < 55˚C
■
After start-up + 5 min:
-
∆
Td
≤
5 K
- Td < Ta + 10˚C
Are repeated 6
times.
Function / description
Starting conditions
F3-error occurs if
the conditions...
Detects too high discharge gas
temperatures.
Td
≥
125˚C for 20 s continuously
Are repeated 6
times.
Input
Connection on
indoor PCB
Connection on
outdoor PCB
Outdoor discharge thermistor
—
R3T-X6A
Outdoor heat exchanger thermistor
—
R2T-X5A
Indoor heat exchanger thermistor
R2T-X18A
—
Summary of Contents for FHC45BZ7V1
Page 1: ...ESIE02 01 Service Manual Sky Air R 407C B series SV p p p...
Page 2: ......
Page 3: ...ESIE02 01 Service Manual Sky Air R 407C B series SV p p p...
Page 4: ......
Page 16: ...Introduction ESIE02 01 xii 3 1 4 5...
Page 18: ...ESIE02 01 1 2 Part 1 System Outline 3 1 1 5...
Page 42: ...General Outline Outdoor Units ESIE02 01 1 26 Part 1 System Outline 3 1 1 4 5...
Page 49: ...ESIE02 01 General Outline Indoor Units Part 1 System Outline 1 33 3 1 4 5...
Page 72: ...General Outline Indoor Units ESIE02 01 1 56 Part 1 System Outline 3 1 1 4 5...
Page 86: ...Specifications ESIE02 01 1 70 Part 1 System Outline 3 1 1 4 5...
Page 110: ...ESIE02 01 1 94 Part 1 System Outline...
Page 130: ...Switch Box Layout ESIE02 01 1 114 Part 1 System Outline 3 1 1 4 5...
Page 180: ...PCB Layout ESIE02 01 1 164 Part 1 System Outline 3 1 1 4 5...
Page 182: ...ESIE02 01 2 2 Part 2 Functional Description 3 1 2 5...
Page 204: ...General Functionality ESIE02 01 2 24 Part 2 Functional Description 3 1 2 4 5...
Page 216: ...Overview of the cooling mode functions ESIE02 01 2 36 Part 2 Functional Description 3 1 2 4 5...
Page 232: ...ESIE02 01 3 2 Part 3 Troubleshooting 3 1 3 5...
Page 294: ...Error Codes System Malfunctions ESIE02 01 3 64 Part 3 Troubleshooting 3 1 3 4 5...