Error Codes: System Malfunctions
ESIE02–01
3–54
Part 3 – Troubleshooting
3
1
3
4
5
4.2
Gas Shortage Detection (
U0
)
Error code
U0
LED indication
The table below shows the LED indication.
Error method
The discharge pipe thermistor detects the malfunction temperature at which there can be a gas
shortage. If the discharge temperature exceeds 125˚C during more than 20 s, the outdoor unit will stop
and retry when the guard timer is OFF (3 min have passed).
During the retrial, the expansion valve will be opened 90 pulses more than in case of the previous start.
When the unit restarts with a fully opened expansion valve, the remote control displays “U0” after
pressing the test button.
Error generation
The error is generated when the microcomputer detects gas shortage. However, the unit can still
operate.
Causes
The possible causes are:
■
Refrigerant shortage
■
Clogging of the refrigerant piping circuit.
Troubleshooting
To troubleshoot, proceed as follows:
Operation
HAP (green)
H1P (red)
H2P (red)
Normal
6
8
8
Malfunctioning
—
—
—
Check the amount of
refrigerant.
No
Is it correct?
Fill with the proper
amount of refrigerant.
Ÿ
Check the refrigerant piping
circuit for clogging.
Ÿ
Check the expansion valve.
Refer to error
E9
.
Ÿ
Check the discharge thermistor.
Refer to error
F3
.
Yes
Summary of Contents for FHC45BZ7V1
Page 1: ...ESIE02 01 Service Manual Sky Air R 407C B series SV p p p...
Page 2: ......
Page 3: ...ESIE02 01 Service Manual Sky Air R 407C B series SV p p p...
Page 4: ......
Page 16: ...Introduction ESIE02 01 xii 3 1 4 5...
Page 18: ...ESIE02 01 1 2 Part 1 System Outline 3 1 1 5...
Page 42: ...General Outline Outdoor Units ESIE02 01 1 26 Part 1 System Outline 3 1 1 4 5...
Page 49: ...ESIE02 01 General Outline Indoor Units Part 1 System Outline 1 33 3 1 4 5...
Page 72: ...General Outline Indoor Units ESIE02 01 1 56 Part 1 System Outline 3 1 1 4 5...
Page 86: ...Specifications ESIE02 01 1 70 Part 1 System Outline 3 1 1 4 5...
Page 110: ...ESIE02 01 1 94 Part 1 System Outline...
Page 130: ...Switch Box Layout ESIE02 01 1 114 Part 1 System Outline 3 1 1 4 5...
Page 180: ...PCB Layout ESIE02 01 1 164 Part 1 System Outline 3 1 1 4 5...
Page 182: ...ESIE02 01 2 2 Part 2 Functional Description 3 1 2 5...
Page 204: ...General Functionality ESIE02 01 2 24 Part 2 Functional Description 3 1 2 4 5...
Page 216: ...Overview of the cooling mode functions ESIE02 01 2 36 Part 2 Functional Description 3 1 2 4 5...
Page 232: ...ESIE02 01 3 2 Part 3 Troubleshooting 3 1 3 5...
Page 294: ...Error Codes System Malfunctions ESIE02 01 3 64 Part 3 Troubleshooting 3 1 3 4 5...