Error Codes: Outdoor Units
ESIE02–01
3–36
Part 3 – Troubleshooting
3
1
3
4
5
The fan does not
rotate
To troubleshoot, proceed as follows:
1
Remove obstacles so the
fan rotates correctly or
replace the fan.
2
Reconnect connector.
Try to rotate the
fan with your
hand.
Can
you rotate the
fan smoothly?
No
Check capacitor
Yes
Is
the capacitor in
good condition?
Yes
1
Replace the capacitor.
2
Reconnect connector.
No
The fan does not
rotate.
Check outdoor
unit type.
Is the unit a
R(Y)P71B?
The unit is a
R(Y)P100-125B
No
Disconnect
connector X14 on
outdoor unit PCB.
Disconnect
connectors X14A
and X15A on
outdoor unit PCB.
Yes
1
Check motor windings.
2
Reconnect connector.
Summary of Contents for FHC45BZ7V1
Page 1: ...ESIE02 01 Service Manual Sky Air R 407C B series SV p p p...
Page 2: ......
Page 3: ...ESIE02 01 Service Manual Sky Air R 407C B series SV p p p...
Page 4: ......
Page 16: ...Introduction ESIE02 01 xii 3 1 4 5...
Page 18: ...ESIE02 01 1 2 Part 1 System Outline 3 1 1 5...
Page 42: ...General Outline Outdoor Units ESIE02 01 1 26 Part 1 System Outline 3 1 1 4 5...
Page 49: ...ESIE02 01 General Outline Indoor Units Part 1 System Outline 1 33 3 1 4 5...
Page 72: ...General Outline Indoor Units ESIE02 01 1 56 Part 1 System Outline 3 1 1 4 5...
Page 86: ...Specifications ESIE02 01 1 70 Part 1 System Outline 3 1 1 4 5...
Page 110: ...ESIE02 01 1 94 Part 1 System Outline...
Page 130: ...Switch Box Layout ESIE02 01 1 114 Part 1 System Outline 3 1 1 4 5...
Page 180: ...PCB Layout ESIE02 01 1 164 Part 1 System Outline 3 1 1 4 5...
Page 182: ...ESIE02 01 2 2 Part 2 Functional Description 3 1 2 5...
Page 204: ...General Functionality ESIE02 01 2 24 Part 2 Functional Description 3 1 2 4 5...
Page 216: ...Overview of the cooling mode functions ESIE02 01 2 36 Part 2 Functional Description 3 1 2 4 5...
Page 232: ...ESIE02 01 3 2 Part 3 Troubleshooting 3 1 3 5...
Page 294: ...Error Codes System Malfunctions ESIE02 01 3 64 Part 3 Troubleshooting 3 1 3 4 5...