Overview of the cooling mode functions
ESIE02–01
2–28
Part 2 – Functional Description
3
1
2
4
5
Integral capacity
The illustration below shows the integral capacity in function of the compressor running time.
Mode 0
Intelligent control mode
When the DIP switches are in mode 0, “intelligent freeze-up prevention control” determines the
freeze-up activation. The outdoor unit can determine the freeze-up activation.
Mode 1
Disabled intelligent control mode
The table below contains the freeze-up conditions, these are the same as for the Sky Air G- and
K-series.
Mode 2
Added countermeasure to avoid ice/water blow out during freeze-up cycle.
Mode 2 enables the possibility to start a freeze-up activation decision by the outdoor unit, but with
more severe conditions than in mode 0.
Mode 3
Mode 3 is used in case mode 2 is insufficient as countermeasure.
Integral
capacity
Cooling or dry keep
Freeze-up operation
Diminishing
integral capacity
Max. integral
capacity value
Compr. ON time
Condition
(OR)
Evap. temp.
Timers
Remarks
1
-1˚C
40 min compressor accumu-
lated time
—
2
-3˚C
Te
≤
-3˚C for 1 min continu-
ously after minimum 8 min of
operation
Only for FHYP
3
-5˚C
Te
≤
-5˚C for 1 min continu-
ously after minimum 8 min of
operation
For indoor units other than FHYP
Model
Used in case of...
FAY
Reverse angle installation for water drain flow.
4-way cassette
2- or 3-way air outlet.
Summary of Contents for FHC45BZ7V1
Page 1: ...ESIE02 01 Service Manual Sky Air R 407C B series SV p p p...
Page 2: ......
Page 3: ...ESIE02 01 Service Manual Sky Air R 407C B series SV p p p...
Page 4: ......
Page 16: ...Introduction ESIE02 01 xii 3 1 4 5...
Page 18: ...ESIE02 01 1 2 Part 1 System Outline 3 1 1 5...
Page 42: ...General Outline Outdoor Units ESIE02 01 1 26 Part 1 System Outline 3 1 1 4 5...
Page 49: ...ESIE02 01 General Outline Indoor Units Part 1 System Outline 1 33 3 1 4 5...
Page 72: ...General Outline Indoor Units ESIE02 01 1 56 Part 1 System Outline 3 1 1 4 5...
Page 86: ...Specifications ESIE02 01 1 70 Part 1 System Outline 3 1 1 4 5...
Page 110: ...ESIE02 01 1 94 Part 1 System Outline...
Page 130: ...Switch Box Layout ESIE02 01 1 114 Part 1 System Outline 3 1 1 4 5...
Page 180: ...PCB Layout ESIE02 01 1 164 Part 1 System Outline 3 1 1 4 5...
Page 182: ...ESIE02 01 2 2 Part 2 Functional Description 3 1 2 5...
Page 204: ...General Functionality ESIE02 01 2 24 Part 2 Functional Description 3 1 2 4 5...
Page 216: ...Overview of the cooling mode functions ESIE02 01 2 36 Part 2 Functional Description 3 1 2 4 5...
Page 232: ...ESIE02 01 3 2 Part 3 Troubleshooting 3 1 3 5...
Page 294: ...Error Codes System Malfunctions ESIE02 01 3 64 Part 3 Troubleshooting 3 1 3 4 5...