ESIE02–01
Overview of the cooling mode functions
Part 2 – Functional Description
2–27
3
2
4
5
1
2.3
Freeze-Up Function in Cooling or Dry Keep
Applicable units
■
R(Y)P71-250B
■
FHYCP, FHYBP, FDYP, FUYP, FAYP and FHYKP
Starting conditions
In order to avoid formation of ice on the indoor heat exchanger in cooling and dry mode, the system
automatically starts up a freeze-up cycle when a number of specific conditions are fulfilled.
Starting conditions 1
■
The compressor has been running for less than
A
min.
■
The integral cooling capacity decreases for 200 s continuously (see integral capacity calculation
further in this section).
■
Te < -1˚C for 1 min continuously (0˚C for FAY indoor units).
Starting conditions 2 (FAYP indoor units)
■
The compressor has been running for more than
A
min.
■
The integral cooling capacity decreases for
B
s continuously and Te <
F
˚C for 1 min continuously
(see integral capacity calculation further in this section),
or
Te < -1˚C for 1 min continuously.
Starting conditions 2 (not-FAYP indoor units)
■
The compressor has been running for more than
A
min.
■
The integral cooling capacity decreases for
B
s continuously (see integral capacity calculation
further in this section).
■
Te <
C
˚C for 1 min continuously.
Starting condition 3
■
Te <
D
˚C for
E
min accumulated.
Starting conditions 4
■
The compressor has been running for more than 1 min continuously while Te
≤
-5˚C.
■
Compressor ON
→
OFF.
Starting conditions 5
■
The compressor has been running for more than 8 min continuously while
the outdoor ambient temp. < -2.9 x room temp. + 79˚C.
■
The compressor has been running for more than 8 min continuously while Te < -5˚C for 1 min
continuously.
A, B, C, D, E and F
The table below contains the values of A, B, C, D, E and F in function of the DIP switch settings on the
outdoor PCB.
Mode
DIP switch
A
B
C
D
E
F
2-3
2-4
0
OFF
OFF
20 min
100 s
-1˚C
-1˚C
25 min
0˚C
1
ON
2
OFF
ON
8 min
0 s
0˚C
+1˚C
15 min
3
ON
5 min
+2˚C
+3˚C
+2˚C
Summary of Contents for FHC45BZ7V1
Page 1: ...ESIE02 01 Service Manual Sky Air R 407C B series SV p p p...
Page 2: ......
Page 3: ...ESIE02 01 Service Manual Sky Air R 407C B series SV p p p...
Page 4: ......
Page 16: ...Introduction ESIE02 01 xii 3 1 4 5...
Page 18: ...ESIE02 01 1 2 Part 1 System Outline 3 1 1 5...
Page 42: ...General Outline Outdoor Units ESIE02 01 1 26 Part 1 System Outline 3 1 1 4 5...
Page 49: ...ESIE02 01 General Outline Indoor Units Part 1 System Outline 1 33 3 1 4 5...
Page 72: ...General Outline Indoor Units ESIE02 01 1 56 Part 1 System Outline 3 1 1 4 5...
Page 86: ...Specifications ESIE02 01 1 70 Part 1 System Outline 3 1 1 4 5...
Page 110: ...ESIE02 01 1 94 Part 1 System Outline...
Page 130: ...Switch Box Layout ESIE02 01 1 114 Part 1 System Outline 3 1 1 4 5...
Page 180: ...PCB Layout ESIE02 01 1 164 Part 1 System Outline 3 1 1 4 5...
Page 182: ...ESIE02 01 2 2 Part 2 Functional Description 3 1 2 5...
Page 204: ...General Functionality ESIE02 01 2 24 Part 2 Functional Description 3 1 2 4 5...
Page 216: ...Overview of the cooling mode functions ESIE02 01 2 36 Part 2 Functional Description 3 1 2 4 5...
Page 232: ...ESIE02 01 3 2 Part 3 Troubleshooting 3 1 3 5...
Page 294: ...Error Codes System Malfunctions ESIE02 01 3 64 Part 3 Troubleshooting 3 1 3 4 5...