9

English

<In case of sticking vinyl tape>

Tightened part

Appro

x.

 90°

Stick vinyl tape to prevent 

the sealing material 

(Large) (10) from tearing.

Vinyl tape
(Field supply)

<In case of bending the tip>

Bend the tip to prevent the sealing 
material (Large) (10) from tearing.

Tightened part

Appro

x.

 90°

Fig. 16

< Caution to be taken when carrying out upward drain 

piping (Refer to Fig. 17) >

• 

The maximum height of the drain riser is 26-1/2 in. 
(675 mm). Since the drain pump mounted on this indoor 

unit is a high head type, from the characteristic point of 
view, the higher the drain riser the lower the draining noise. 
Therefore, the drain riser of 11-3/4 in. (300 mm) or higher is 
recommended.

•  For upward drain piping, keep the horizontal piping dis-

tance of 11-3/4 in. (300 mm) or less between the drain 
socket root to the drain riser.

Ceiling slab

≤ 

11-3/4 (300)

3-5 ft. (1-1.5 m)

Support

[Unit: in. (mm)]

Metal clamp (2) (Accessory)

Drain hose (1) (Accessory)

Upward drain piping

Drain riser

Adjustable
(

≤ 

26-1/2 (675))

(

≤ 

33-1/2 (850))

Drain hose (1) 
(Accessory)

Level or upward 

inclination

Keep the drain hose level or make a slight upward 

inclination so that air may not stagnate in the drain hose.

If air stagnates, the drain may flow oppositely when the 

drain pump stops and generate an abnormal sound.   

Fig. 17

 CAUTION

• 

Do not apply excessive force to the attached drain hose 

(1) by bending or twisting it. 
This could cause water leakage.

•  In case of centralized drain piping, carry out piping work 

according to the procedure shown in the fol lowing 

Fig. 18.

Make a downward inclination of 1/100 

or more to avoid stagnancy of air.

0 to 26-1/2 in. (0 – 675 mm)

Centralized drain piping

If water stagnates in the drain 

piping, it may cause clogging of 

drain piping. 

Fig. 18

•  Select a size for the centralized drain piping that meets 

the capacity of indoor units to be con nected. Refer to the 
technical document.

•  When installing the new indoor unit, use the attached 

new drain hose (1) and the metal clamp (2). 
If an old drain hose or a metal clamp is used, it may 
cause water leakage.

(2) 

After piping work is finished, check if the drain flows 

smoothly.

[When the electric wiring work is finished]

•  Gradually pour 1/4 gal. (1  ) of water from the air outlet 

on the left side of the drain socket into the drain pan 
using caution to avoid splashing water on the electric 

components such as the drain pump. Confirm drainage 

by operating the indoor unit under cooling mode ac-
cording to 

9. FIELD SETTING and 10. TEST OPERA-

TION. (Refer to Fig. 19)

≥4 in.

 (100 mm)

Plastic container for pouring water
(Tube length of 4 in. (100 mm) or 
more is necessary.)

Drain outlet for service 

(with rubber plug)

Drain piping

Use it when draining water 

in the drain pan

[Method of adding water]

Fig. 19

01_EN_3P693452-2.indd   9

2022/08/09   16:00:12

Summary of Contents for FCQ18AAVJU

Page 1: ...wner Lire soigneusement ces instructions avant l installation Conserver ce manuel port e de main pour r f rence ult rieure Ce manuel doit tre donn au propri taire de l quipement Lea cuidadosamente est...

Page 2: ...use severe injury or death After completing the installation work check that the refrigerant gas does not leak throughout the system Do not install unit in an area where flammable materials are presen...

Page 3: ...e earth s protection again harmful ultraviolet radiation R410A can contribute to the greenhouse effect if it is released Therefore take proper measures to check for the tightness of the refrigerant pi...

Page 4: ...ity from the body when carrying out wiring and the control box cover is removed The electric parts may be damaged 1 1 ACCESSORIES Check if the following accessories are attached to the indoor unit Nam...

Page 5: ...set the fan speed at thermostat OFF did you explain the set fan speed to the cus tomer Have you handed the operation manual and the installation manual to the customer Points of the operation explana...

Page 6: ...center of the sensing area is located in the center of the product 32 in 800 mm above the floor in case of the infrared presence sensor or 0 in 0 mm above the floor in case of the infrared floor sens...

Page 7: ...pening dimension Make the ceiling opening required for installation at the installation location and carry out refrigerant drain pip ing power supply wiring remote controller wiring and transmission w...

Page 8: ...ndoor unit with four screws 6 At this time put the installation pattern paper 5 to the indoor unit with the triangle marks on the indoor unit and those on the installation pattern paper 5 aligned Inst...

Page 9: ...efrigerant leakage To prevent contamination or moisture from getting into the piping take measures such as pinch ing or taping the piping Do not mix substance other than the specified refrig erant suc...

Page 10: ...n Union joint Refrigerant piping Joint insulating material 9 Accessory Piping holding plate screw 2 locations Gas piping Liquid piping Liquid piping insulating method Indoor unit Indoor unit Clamp 4 A...

Page 11: ...ng of piping due to residue 6 DRAIN PIPING WORK 1 Carry out drain piping Carry out drain piping so that drainage can be ensured Select the piping diameter equal to or larger than except for riser that...

Page 12: ...ot apply excessive force to the attached drain hose 1 by bending or twisting it This could cause water leakage In case of centralized drain piping carry out piping work according to the procedure show...

Page 13: ...terial 14 to perform the thermal insulation of the drain socket Do not connect the drain piping directly to the sewage that gives off ammonia odor The ammonia in the sewage may go through the drain pi...

Page 14: ...or insulate the wirings properly Insulation sleeve Ring type crimp style terminal Wiring Use the required wires connect and fix securely so that external force may not apply to the terminals Use a pr...

Page 15: ...pply wiring grounding wiring X2M Terminal block for remote controller wiring transmission wiring X1M Printed Circuit Board Forced off Remote controller wiring X1M Transmission wiring X1M Remote contro...

Page 16: ...1 system When using 1 remote controller Normal operation Indoor unit Power supply single phase 60Hz 208 230V Outdoor unit Remote controller L1L2 IN D OUT D F1 F2 F1 F2 P1 P2 P1 P2 F1 F2 T1 T2 Control...

Page 17: ...If test operation is carried out before mounting the decora tion panel check the horizontal blade action after the panel is mounted 9 FIELD SETTING Refer to also the installation manual attached to th...

Page 18: ...Differential MODE NO FIRST CODE NO SECOND CODE NO 1 8 F 1 C 12 22 2 01 0 9 F 0 5 C 02 9 7 SETTING AIR DISCHARGE DIRECTION When changing air discharge setting 2 way or 3 way air discharge set the SECON...

Page 19: ...the air conditioner until the interior finish work is completed If the air conditioner is operated the inside of the indoor units may be polluted by substances generated from the coating and adhesives...

Page 20: ...2209 HT 3P693452 2 EM21A045 Daikin Texas Technology Park 19001 Kermier Road Waller TX 77484 U S A 00_CV_3P693452 2 indd 2 2022 07 07 16 49 30...

Reviews: