background image

3

English

[unit: in. (mm)]

60 (1,500) 

or more

80 (2,000) or more

160 (4,000) or more

Indoor unit

Indoor unit

Exhaust fan

(NOTE 1)

Lighting

*60 (1,500) 

or more

At le

ast 60 

(1,500)

from 

a

ny fi

xture

Obstacles

From the 

wall

If the air outlet is in a close proximity to 

both sides of the wall surface in a corner 

installation etc., the distance of at least 

80 in. (2,000 mm) is recommended

(NOTE2)

Fig. 2

NOTE 

1.  If the air passage is obstructed, or if the installation space 

requirements are not met, performance may decrease or 

the thermostat may easily turn off due to reduced airflow 

rate and intake of discharged air.

2. 

In a roadside store or restaurant, the air flows in the order of 

outdoor 

 attic 

 living space because the ventilation sys-

tem creates negative pressure in living space. As a result, 
condensation may arise since the temperature and humid-
ity around the indoor unit become similar to the outdoor 
environment due to direct intake of outside air into the attic.

 CAUTION

• 

Any vents, light fixtures, or other appliances which may 
disturb the airflow might soil the ceiling if too close, so fol

-

low 

Fig. 2 when installing.

Note)

1.  This restriction applies to the exposed type lighting, 

but does not apply to the recessed type, which does 
not protrude below the ceiling line.

2.  The clearance from the wall (indicated with *) must be 20 in. 

(500 mm) or more if the air outlet is closed or the horizontal 

blade is set to Airflow block and, if the corners (left and right 

corners of the target air outlet) are also closed by 8 in. (200 
mm) or more. 

For how to set the airflow direction (including Airflow block) 

with the horizontal blade, refer to 

Individual Airflow Direc

-

tion in the operation manual attached to the remote controller.

•  Install the indoor and outdoor units, power supply wiring, 

remote controller wiring and transmission wiring at least 
40 in. (1 m) away from televisions or radios to prevent im-
age interference or noise. 
(Depending on the radio waves, a distance of 40 in. (1 m) 

may not be sufficient to eliminate the noise.)

• 

Install the indoor unit as far as possible from fluorescent lamps.

•  Localized temperature difference from the room temperature, 

if too large, can affect how the infrared floor sensor judges.

 

(This may occur, for example, in an area where floor heating/

high-temperature heat generating equipment is installed.)

•  Each sensor has been set so that the center of the sensing 

area is located in the center of the product 32 in. (800 mm) 

above the floor (in case of the infrared presence sensor) or 0 
in. (0 mm) above the floor (in case of the infrared floor sensor) 
when the ceiling height is approximately 8-3/4 ft. (2.7 m).

(2)  Ceiling height

•  This indoor unit can be installed in a space of which 

ceiling height is up to 11-1/2 ft. (3.5 m) (Type 30 · 36 · 42 · 
48: 13-3/4 ft. (4.2 m))

• 

However, if the ceiling height exceeds 8-3/4 ft. (2.7 m) 

(Type 30~48: 10-1/2 ft. (3.2 m)), it is necessary to set 
from the remote controller on site. Refer to the section 
9. FIELD SETTING and 10. TEST OPERATION.

(3)  Direction of the air discharge

•  Select the number of directions of the optimum air 

discharge for the shape or the position of the room.

•  The number of directions of the air discharge can be 

changed by installing a sealing material.

• 

When installing a sealing material, the field setting 

from the remote controller is required. For details, 
refer to the installation manual attached to the sealing 
materials.
(It is set to the setting position number 

01 (Standard · 

All round outlet) when shipped from the factory.)

•  To use the optional sealing material kit to change the 

setting of air discharge direction (4-way blow type (with 
corners sealed)/3-way blow type/2-way blow type), 
refer to the installation manual attached to it.

*: Refrigerant 

 piping

*

*

*

*

[Direction of air discharge]

All round

4-way

3-way

2-way

Fig. 3

NOTE 

Depending on the temperature, humidity and airflow condi

-

tions in the attic due to the indoor airflow (air draft from ex

-

haust fan, etc.), outside air intake and so on, condensation 
may arise on the ceiling near the corner air outlet.
In that case, close the corner air outlet using the sealing mate-
rial kit (sold separately).

(4)  Use suspension bolts for installation.

Investigate if the installation place can withstand the 
weight of the indoor unit and, if necessary, hang the 
indoor unit with bolts after it is reinforced by beams etc. 
(Refer to the installation pattern paper (5) for the mounting pitch.)

(5) 

Infrared presence/floor sensor’s sensing area

The sensing area is shown in the figure below.

32 in. (800 mm)

h

φ

a

φ

b

[Sensing area]

Infrared floor 

sensor

Infrared 

presence sensor

Infrared presence 

sensor

Infrared floor 

sensor

Piping connection 

side

Drain connection 

side

Indoor unit installation 

height h [ft. (m)]

8-3/4 (2.7)

11-1/2 (3.5)

13 (4.0)

Infrared presence sen-

sor 

f

a [ft. (m)]

Approx. 

 

28 (8.5)

Approx. 

 

37-1/2 (11.5)

Approx. 

 

44-1/2 (13.5)

Infrared floor sensor 

f

[ft. (m)]

Approx. 

 

36 (11)

Approx. 

 

46 (14)

Approx. 

 

52-1/2 (16)

01_EN_3P693452-2.indd   3

2022/08/09   16:00:10

Summary of Contents for FCQ18AAVJU

Page 1: ...wner Lire soigneusement ces instructions avant l installation Conserver ce manuel port e de main pour r f rence ult rieure Ce manuel doit tre donn au propri taire de l quipement Lea cuidadosamente est...

Page 2: ...use severe injury or death After completing the installation work check that the refrigerant gas does not leak throughout the system Do not install unit in an area where flammable materials are presen...

Page 3: ...e earth s protection again harmful ultraviolet radiation R410A can contribute to the greenhouse effect if it is released Therefore take proper measures to check for the tightness of the refrigerant pi...

Page 4: ...ity from the body when carrying out wiring and the control box cover is removed The electric parts may be damaged 1 1 ACCESSORIES Check if the following accessories are attached to the indoor unit Nam...

Page 5: ...set the fan speed at thermostat OFF did you explain the set fan speed to the cus tomer Have you handed the operation manual and the installation manual to the customer Points of the operation explana...

Page 6: ...center of the sensing area is located in the center of the product 32 in 800 mm above the floor in case of the infrared presence sensor or 0 in 0 mm above the floor in case of the infrared floor sens...

Page 7: ...pening dimension Make the ceiling opening required for installation at the installation location and carry out refrigerant drain pip ing power supply wiring remote controller wiring and transmission w...

Page 8: ...ndoor unit with four screws 6 At this time put the installation pattern paper 5 to the indoor unit with the triangle marks on the indoor unit and those on the installation pattern paper 5 aligned Inst...

Page 9: ...efrigerant leakage To prevent contamination or moisture from getting into the piping take measures such as pinch ing or taping the piping Do not mix substance other than the specified refrig erant suc...

Page 10: ...n Union joint Refrigerant piping Joint insulating material 9 Accessory Piping holding plate screw 2 locations Gas piping Liquid piping Liquid piping insulating method Indoor unit Indoor unit Clamp 4 A...

Page 11: ...ng of piping due to residue 6 DRAIN PIPING WORK 1 Carry out drain piping Carry out drain piping so that drainage can be ensured Select the piping diameter equal to or larger than except for riser that...

Page 12: ...ot apply excessive force to the attached drain hose 1 by bending or twisting it This could cause water leakage In case of centralized drain piping carry out piping work according to the procedure show...

Page 13: ...terial 14 to perform the thermal insulation of the drain socket Do not connect the drain piping directly to the sewage that gives off ammonia odor The ammonia in the sewage may go through the drain pi...

Page 14: ...or insulate the wirings properly Insulation sleeve Ring type crimp style terminal Wiring Use the required wires connect and fix securely so that external force may not apply to the terminals Use a pr...

Page 15: ...pply wiring grounding wiring X2M Terminal block for remote controller wiring transmission wiring X1M Printed Circuit Board Forced off Remote controller wiring X1M Transmission wiring X1M Remote contro...

Page 16: ...1 system When using 1 remote controller Normal operation Indoor unit Power supply single phase 60Hz 208 230V Outdoor unit Remote controller L1L2 IN D OUT D F1 F2 F1 F2 P1 P2 P1 P2 F1 F2 T1 T2 Control...

Page 17: ...If test operation is carried out before mounting the decora tion panel check the horizontal blade action after the panel is mounted 9 FIELD SETTING Refer to also the installation manual attached to th...

Page 18: ...Differential MODE NO FIRST CODE NO SECOND CODE NO 1 8 F 1 C 12 22 2 01 0 9 F 0 5 C 02 9 7 SETTING AIR DISCHARGE DIRECTION When changing air discharge setting 2 way or 3 way air discharge set the SECON...

Page 19: ...the air conditioner until the interior finish work is completed If the air conditioner is operated the inside of the indoor units may be polluted by substances generated from the coating and adhesives...

Page 20: ...2209 HT 3P693452 2 EM21A045 Daikin Texas Technology Park 19001 Kermier Road Waller TX 77484 U S A 00_CV_3P693452 2 indd 2 2022 07 07 16 49 30...

Reviews: