9-2  SETTING AIR DISCHARGE DIRECTION

•  Refer to the installation manual attached to the sealing ma-

terial of air discharge outlet sold separately and engineer-
ing data book, for ceiling height settings for four-direction 
(part of corner closed off) and three-direction. 
(The SECOND CODE NO. is factory set to 

01 (all round 

outlet) before shipping.)

9-3  SETTING WHEN AN OPTIONAL ACCESSORY 

IS ATTACHED

•  For setting when attaching an optional accessory, refer to 

the installation manual attached to the optional accessory.

9-4  SETTING FAN SPEED DURING THERMOSTAT 

OFF

•  Set the fan speed according to the using environment after 

consultation with your customer.

• 

When the fan speed is changed, explain the set fan speed 

to your customer.

Table 5

Setting

MODE 

NO.

FIRST 

CODE NO.

SECOND 

CODE NO.

Fan speed during 

cooling  

thermostat OFF

LL  

(Extra low)

12 (22)

6

01

Setting

02

Fan speed during 

heating  

thermostat OFF

LL  

(Extra low)

12 (22)

3

01

Setting

02

9-5  SETTING FILTER SIGN

• 

A message to inform the air filter cleaning time will be indi

-

cated on the remote controller.

•  Set the SECOND CODE NO. shown in the Table 6 accord-

ing to the amount of dust or pollution in the room.

• 

Though the indoor unit is equipped with the long life filter, it 
is necessary to periodically clean the filter to avoid clogging 
of the filter. Please also explain the set time to the customer.

• 

The periodic filter-cleaning time can be shortened depend

-

ing on the environment.

Table 6

Contamination

Hours until 

indication

MODE 

NO.

FIRST 

CODE NO.

SECOND 

CODE 

NO.

Normal

Approx. 

 

2,500 hrs

10 (20)

0

01

More  

contaminated

Approx. 

 

1,250 hrs

02

With indication

3

01

No indication*

02

* Use 

No indication setting when cleaning indication is not neces-

sary such as the case of periodical clean ing being carried out.

9-6  SETTING THERMOSTAT DIFFERENTIAL

•  For setting when remote sensor is used, change over ther-

mostat differential.

Table 7

Differential

MODE 

NO.

FIRST 

CODE NO.

SECOND 

CODE 

NO.

1.8°F (1°C)

12 (22)

2

01

0.9°F (0.5°C)

02

9-7  SETTING AIR DISCHARGE DIRECTION

•  When changing air discharge setting (2-way or 3-way air 

discharge), set the SECOND CODE NO. as shown in the 
Table 8.

Table 8

Setting

MODE 

NO.

FIRST 

CODE NO.

SECOND 

CODE 

NO.

4-way air  

discharge

13 (23)

1

01

3-way air  

discharge

02

2-way air  

discharge

03

9-8  DRY MODE SETTING

Table 9

Setting

MODE 

NO.

FIRST 

CODE NO.

SECOND 

CODE 

NO.

Dry mode set 

temperature

Room  

temperature

11 (21)

12

01

Same as cool-

ing mode set  

temperature

02

10. TEST OPERATION

•  After cleaning the indoor unit inside, carry out test operation 

according to installation manual attached to the outdoor unit.

• 

When the remote controller operation lamp flashes, it 

shows that something is abnormal. 
Check the malfunction codes on the remote controller. 
The relation between the malfunction codes and malfunc-
tion details is described in the operation manual attached to 
the outdoor unit. 
Particularly, if the indication is one of those shown in the 
Table 10, it may be an error in the electrical wiring or the 
power supply is disconnected. Therefore, recheck wiring.

Table 10

Remote controller 

indication

Details

Though the central-

ized control is not 

carried out, the 

indicating the central 

control turns on. 

• 

The terminals (T1 · T2) for FORCED OFF 
on the indoor unit trans mission terminal 
block is short circuited.

[U4] displays.

[UH] displays.

• 

The power supply to the outdoor unit is not 
made. 

• 

The power supply work to the outdoor unit 
is not carried out.

• 

The transmission wiring and the remote 
controller wiring and FORCED OFF wiring 
are connected incorrectly.

• 

The transmission wiring is disconnected. 

No indication

• 

The power supply to the indoor unit is not 
made. 

• 

The power supply work to the indoor unit is 
not carried out.

• 

The remote controller wiring and the trans-
mission wiring and FORCED OFF wiring 
are connected incorrectly.

• 

The remote controller wiring is discon-
nected.

•  At test operation, install the decoration panel and check the 

actuation of the horizontal blade.

01_EN_3P693452-2.indd   15

2022/08/09   16:00:15

Summary of Contents for FCQ18AAVJU

Page 1: ...wner Lire soigneusement ces instructions avant l installation Conserver ce manuel port e de main pour r f rence ult rieure Ce manuel doit tre donn au propri taire de l quipement Lea cuidadosamente est...

Page 2: ...use severe injury or death After completing the installation work check that the refrigerant gas does not leak throughout the system Do not install unit in an area where flammable materials are presen...

Page 3: ...e earth s protection again harmful ultraviolet radiation R410A can contribute to the greenhouse effect if it is released Therefore take proper measures to check for the tightness of the refrigerant pi...

Page 4: ...ity from the body when carrying out wiring and the control box cover is removed The electric parts may be damaged 1 1 ACCESSORIES Check if the following accessories are attached to the indoor unit Nam...

Page 5: ...set the fan speed at thermostat OFF did you explain the set fan speed to the cus tomer Have you handed the operation manual and the installation manual to the customer Points of the operation explana...

Page 6: ...center of the sensing area is located in the center of the product 32 in 800 mm above the floor in case of the infrared presence sensor or 0 in 0 mm above the floor in case of the infrared floor sens...

Page 7: ...pening dimension Make the ceiling opening required for installation at the installation location and carry out refrigerant drain pip ing power supply wiring remote controller wiring and transmission w...

Page 8: ...ndoor unit with four screws 6 At this time put the installation pattern paper 5 to the indoor unit with the triangle marks on the indoor unit and those on the installation pattern paper 5 aligned Inst...

Page 9: ...efrigerant leakage To prevent contamination or moisture from getting into the piping take measures such as pinch ing or taping the piping Do not mix substance other than the specified refrig erant suc...

Page 10: ...n Union joint Refrigerant piping Joint insulating material 9 Accessory Piping holding plate screw 2 locations Gas piping Liquid piping Liquid piping insulating method Indoor unit Indoor unit Clamp 4 A...

Page 11: ...ng of piping due to residue 6 DRAIN PIPING WORK 1 Carry out drain piping Carry out drain piping so that drainage can be ensured Select the piping diameter equal to or larger than except for riser that...

Page 12: ...ot apply excessive force to the attached drain hose 1 by bending or twisting it This could cause water leakage In case of centralized drain piping carry out piping work according to the procedure show...

Page 13: ...terial 14 to perform the thermal insulation of the drain socket Do not connect the drain piping directly to the sewage that gives off ammonia odor The ammonia in the sewage may go through the drain pi...

Page 14: ...or insulate the wirings properly Insulation sleeve Ring type crimp style terminal Wiring Use the required wires connect and fix securely so that external force may not apply to the terminals Use a pr...

Page 15: ...pply wiring grounding wiring X2M Terminal block for remote controller wiring transmission wiring X1M Printed Circuit Board Forced off Remote controller wiring X1M Transmission wiring X1M Remote contro...

Page 16: ...1 system When using 1 remote controller Normal operation Indoor unit Power supply single phase 60Hz 208 230V Outdoor unit Remote controller L1L2 IN D OUT D F1 F2 F1 F2 P1 P2 P1 P2 F1 F2 T1 T2 Control...

Page 17: ...If test operation is carried out before mounting the decora tion panel check the horizontal blade action after the panel is mounted 9 FIELD SETTING Refer to also the installation manual attached to th...

Page 18: ...Differential MODE NO FIRST CODE NO SECOND CODE NO 1 8 F 1 C 12 22 2 01 0 9 F 0 5 C 02 9 7 SETTING AIR DISCHARGE DIRECTION When changing air discharge setting 2 way or 3 way air discharge set the SECON...

Page 19: ...the air conditioner until the interior finish work is completed If the air conditioner is operated the inside of the indoor units may be polluted by substances generated from the coating and adhesives...

Page 20: ...2209 HT 3P693452 2 EM21A045 Daikin Texas Technology Park 19001 Kermier Road Waller TX 77484 U S A 00_CV_3P693452 2 indd 2 2022 07 07 16 49 30...

Reviews: