3.  PREPARATION BEFORE INSTALLATION

(1)  Check the relation of location between the ceiling 

opening and the indoor unit suspension bolts.

1 Decor

ation panel

4 Suspension bolt pitch

3 Indoor unit

2 Ceiling opening

1 Decoration panel

2 Ceiling opening

3 Indoor unit

5 Suspension bolt pitch

Refrigerant 

piping

Suspension 

bolt (×4)

A

Fig. 4

[unit: in. (mm)]

1

37-3/8 (950)

2

33-7/8 – 35-7/8 (860 – 910)

3

33-1/16 (840)

4

30-3/4 (780)

5

28 (710)

Ceiling

arrow view

Hanger bracket 

Fig. 5

Decoration Panel

BYCQ54EEFU

BYCQ54EEGFU

  

in. (mm)

4-15/16 – 5-1/8  

(125 – 130)

8-1/16 – 8-1/4  

(205 – 210)

NOTE 

If the indoor unit is not positioned at the correct height, there 
will be a gap between it and the decoration panel that could 
result in water leakage or abnormal noise.

 CAUTION

Reduce the distance between the unit and ceiling to 
1-3/8 in. (35 mm) or below in order to maintain an over-

lapping panel margin 13/16 in. (20 mm) for the opening 
on the ceiling. If the distance exceeds 1-3/8 in. (35 mm), 

attach ceiling material to the part marked 

 or replace 

the ceiling. 

(Refer to Fig. 6)

Frame

1-3/8 (35)

1-3/8 (35)

33-7/8 to 35-7/8 (860 – 910)

(Ceiling-panel 

overlapping 

dimension)

Ceiling 
material

(Ceiling-opening dimension)

13/16 

(20)

13/16 

(20)

[unit: in. (mm)]

Fig. 6

(2)  Make the ceiling opening required for installation.

•  Use the installation pattern paper (5) matched to the 

ceiling opening dimension.

•  Make the ceiling opening required for installation at the 

installation location and carry out refrigerant/drain pip-
ing, power supply wiring, remote controller wiring and 
transmission wiring. (Refer to each section 

5. REFRIG-

ERANT PIP ING WORK, 6. DRAIN PIPING WORK 
and 

7. ELECTRIC WIRING WORK)

•  After making the opening, it may be necessary to rein-

force the ceiling framework to maintain a level ceiling 
and prevent it from vibrating. 
For details, consult with the builder and interior de-
signer.

(3)  Install the suspension bolts.

(Use a M8-M10 sized bolt or equivalent.)
• 

Use hole-in-anchors for the existing bolts and embed

-

ded inserts or foundation bolts for new bolts, and fix the 
indoor unit firmly to the building so that it may withstand 

the weight of the unit. 
In addition, adjust clearance (2 – 4 in. (50 – 100 mm)) 
from the ceiling in advance.

<Installation examples>

2 – 4 in.

(50 – 100 mm)

Foundation bolt

Suspension bolt

Ceiling slab

Long nut or turn-buckle

Ceiling surface

Note) The above shown parts are all field supply.

4.  INSTALLATION OF INDOOR UNIT

<<It is easy to attach the optional accessories (except for 

decoration panel) before installing the indoor unit. Refer 

to also the installation manual attached to the optional 

accessories.>>

For installation, use the attached accessories and speci-

fied accessories.

[Install the indoor unit in the order of steps (1), (2), (3), (4), (5) 
and (6) in case of a newly built ceiling, or in the order of steps 

(1), (3), (4) and (5) in case of an existing ceiling.]

01_EN_3P693452-2.indd   4

2022/08/09   16:00:11

Summary of Contents for FCQ18AAVJU

Page 1: ...wner Lire soigneusement ces instructions avant l installation Conserver ce manuel port e de main pour r f rence ult rieure Ce manuel doit tre donn au propri taire de l quipement Lea cuidadosamente est...

Page 2: ...use severe injury or death After completing the installation work check that the refrigerant gas does not leak throughout the system Do not install unit in an area where flammable materials are presen...

Page 3: ...e earth s protection again harmful ultraviolet radiation R410A can contribute to the greenhouse effect if it is released Therefore take proper measures to check for the tightness of the refrigerant pi...

Page 4: ...ity from the body when carrying out wiring and the control box cover is removed The electric parts may be damaged 1 1 ACCESSORIES Check if the following accessories are attached to the indoor unit Nam...

Page 5: ...set the fan speed at thermostat OFF did you explain the set fan speed to the cus tomer Have you handed the operation manual and the installation manual to the customer Points of the operation explana...

Page 6: ...center of the sensing area is located in the center of the product 32 in 800 mm above the floor in case of the infrared presence sensor or 0 in 0 mm above the floor in case of the infrared floor sens...

Page 7: ...pening dimension Make the ceiling opening required for installation at the installation location and carry out refrigerant drain pip ing power supply wiring remote controller wiring and transmission w...

Page 8: ...ndoor unit with four screws 6 At this time put the installation pattern paper 5 to the indoor unit with the triangle marks on the indoor unit and those on the installation pattern paper 5 aligned Inst...

Page 9: ...efrigerant leakage To prevent contamination or moisture from getting into the piping take measures such as pinch ing or taping the piping Do not mix substance other than the specified refrig erant suc...

Page 10: ...n Union joint Refrigerant piping Joint insulating material 9 Accessory Piping holding plate screw 2 locations Gas piping Liquid piping Liquid piping insulating method Indoor unit Indoor unit Clamp 4 A...

Page 11: ...ng of piping due to residue 6 DRAIN PIPING WORK 1 Carry out drain piping Carry out drain piping so that drainage can be ensured Select the piping diameter equal to or larger than except for riser that...

Page 12: ...ot apply excessive force to the attached drain hose 1 by bending or twisting it This could cause water leakage In case of centralized drain piping carry out piping work according to the procedure show...

Page 13: ...terial 14 to perform the thermal insulation of the drain socket Do not connect the drain piping directly to the sewage that gives off ammonia odor The ammonia in the sewage may go through the drain pi...

Page 14: ...or insulate the wirings properly Insulation sleeve Ring type crimp style terminal Wiring Use the required wires connect and fix securely so that external force may not apply to the terminals Use a pr...

Page 15: ...pply wiring grounding wiring X2M Terminal block for remote controller wiring transmission wiring X1M Printed Circuit Board Forced off Remote controller wiring X1M Transmission wiring X1M Remote contro...

Page 16: ...1 system When using 1 remote controller Normal operation Indoor unit Power supply single phase 60Hz 208 230V Outdoor unit Remote controller L1L2 IN D OUT D F1 F2 F1 F2 P1 P2 P1 P2 F1 F2 T1 T2 Control...

Page 17: ...If test operation is carried out before mounting the decora tion panel check the horizontal blade action after the panel is mounted 9 FIELD SETTING Refer to also the installation manual attached to th...

Page 18: ...Differential MODE NO FIRST CODE NO SECOND CODE NO 1 8 F 1 C 12 22 2 01 0 9 F 0 5 C 02 9 7 SETTING AIR DISCHARGE DIRECTION When changing air discharge setting 2 way or 3 way air discharge set the SECON...

Page 19: ...the air conditioner until the interior finish work is completed If the air conditioner is operated the inside of the indoor units may be polluted by substances generated from the coating and adhesives...

Page 20: ...2209 HT 3P693452 2 EM21A045 Daikin Texas Technology Park 19001 Kermier Road Waller TX 77484 U S A 00_CV_3P693452 2 indd 2 2022 07 07 16 49 30...

Reviews: