background image

6

English

 CAUTION

•  Install the indoor unit horizontally. 

If the indoor unit is inclined and the drain piping side gets 

high, it may cause malfunction of a float switch and results 

in water leakage.

•  Attach nuts on the upper and lower side of hanger 

bracket. 
If there is no upper nut and the lower nut is over-tightened, 
the hanger bracket and the top plate malfunction and cre-
ate unwanted noise.

• 

Do not insert materials other than those specified 

into the clearance between the hanger bracket and 

the washer for hanger bracket (3). 
Unless the washers are properly attached, the suspen-
sion bolts may come off from the hanger bracket.

 WARNING

The indoor unit must be securely installed on a 

place that can withstand the weight. 

If the strength is insufficient, the indoor unit may fall 

down and cause injuries.

5.  REFRIGERANT PIPING WORK

•  For the outdoor unit refrigerant piping, refer to the installa-

tion manual attached to the outdoor unit.

•  Carry out insulation of both gas and liquid refrigerant piping 

securely. If not insulated, it may cause water leakage. For 
gas piping, use insulation material of which heat resistant 
temperature is not less than 250°F (120°C). 
For use under high humidity, strengthen the insulation ma-
terial for refrigerant piping. If not strengthened, the surface 
of insulation material may sweat.

•  Before installation work, make sure that the refrigerant is 

R410A or operation will malfunction.

 CAUTION

This air conditioner is a dedicated model for refriger-

ant R410A. Make sure to meet the require ments shown 

below and carry out installation work.

• 

Use dedicated piping cutters and flaring tools for 

R410A.

• 

When making a flare connection, coat only the flared 

inner surface with ether oil or ester oil.

• 

Use only the flare nuts attached to the indoor unit. 

If other flare nuts are used, it may cause refrigerant 

leakage.

•  To prevent contamination or moisture from getting 

into the piping, take measures such as pinch ing or 

taping the piping.

Do not mix substance other than the specified refrig

-

erant such as air into the refrigeration circuit. 

If the refrigerant leaks during the work, ventilate the 

room.

•  The refrigerant is pre-charged in the outdoor unit.

•  When connecting the piping to the air conditioner, make 

sure to use a spanner and a torque wrench as shown in 
Fig. 10.

• 

Using a tool other than a spanner may destroy the flare 

nut thread, resulting in refrigerant leakage due to poor 
tightening.

• 

For the dimension of flared part and the tightening 

torque, refer to the Table 2.

• 

Use the flare nuts attached to the piping of indoor unit.

• 

When making a flare connection, coat only the flared 

inner surface with ether oil or ester oil.  
(Refer to Fig. 11) 

Then, turn the flare nut 3 to 4 times with your hand and 

screw in the nut.

 

Torque wrench

Spanner

Flare nut

Union joint

Fig. 10

Coat only the flared inner 

surface with ether oil or ester oil

Fig. 11

Table 2

Piping 

size 

[in. (mm)]

Tightening 

torque 

[lbf·ft. (N·m)]

Dimension for 

processing flare 

A [in. (mm)]

Flare shape

[in. (mm)]

f

 3/8 

(9.5)

24.1 – 29.4

(36.3±3.6)

0.504 – 0.520

(13.0±0.2)

R0.016-0.031

(0.4-0.8)

90°±2°

A

45°±2°

f

 5/8 

(15.9)

45.6 – 55.6

(68.6±6.8)

0.760 – 0.776

(19.5±0.2)

 CAUTION

Do not let oil adhere to the screw fixing part of resin 

parts.
If oil adheres, it may weaken the strength of screwed part.

Do not tighten flare nuts too much.

If a flare nut cracks, the refrigerant may leak.

•  If there is no torque wrench, use Table 3 as a rule of 

thumb. 

When tightening the flare nut with a spanner harder and 

harder, there is a point where the tightening torque sud-
denly increases. 
From that position, tighten the nut additionally the angle 
shown in Table 3. 

After the work is finished, check securely that there is no 

gas leak. 
If the nut is not tightened as instructed, it may cause 
slow refrigerant leak and result in malfunction (such as 
does not cool or heat).

01_EN_3P693452-2.indd   6

2022/08/09   16:00:11

Summary of Contents for FCQ18AAVJU

Page 1: ...wner Lire soigneusement ces instructions avant l installation Conserver ce manuel port e de main pour r f rence ult rieure Ce manuel doit tre donn au propri taire de l quipement Lea cuidadosamente est...

Page 2: ...use severe injury or death After completing the installation work check that the refrigerant gas does not leak throughout the system Do not install unit in an area where flammable materials are presen...

Page 3: ...e earth s protection again harmful ultraviolet radiation R410A can contribute to the greenhouse effect if it is released Therefore take proper measures to check for the tightness of the refrigerant pi...

Page 4: ...ity from the body when carrying out wiring and the control box cover is removed The electric parts may be damaged 1 1 ACCESSORIES Check if the following accessories are attached to the indoor unit Nam...

Page 5: ...set the fan speed at thermostat OFF did you explain the set fan speed to the cus tomer Have you handed the operation manual and the installation manual to the customer Points of the operation explana...

Page 6: ...center of the sensing area is located in the center of the product 32 in 800 mm above the floor in case of the infrared presence sensor or 0 in 0 mm above the floor in case of the infrared floor sens...

Page 7: ...pening dimension Make the ceiling opening required for installation at the installation location and carry out refrigerant drain pip ing power supply wiring remote controller wiring and transmission w...

Page 8: ...ndoor unit with four screws 6 At this time put the installation pattern paper 5 to the indoor unit with the triangle marks on the indoor unit and those on the installation pattern paper 5 aligned Inst...

Page 9: ...efrigerant leakage To prevent contamination or moisture from getting into the piping take measures such as pinch ing or taping the piping Do not mix substance other than the specified refrig erant suc...

Page 10: ...n Union joint Refrigerant piping Joint insulating material 9 Accessory Piping holding plate screw 2 locations Gas piping Liquid piping Liquid piping insulating method Indoor unit Indoor unit Clamp 4 A...

Page 11: ...ng of piping due to residue 6 DRAIN PIPING WORK 1 Carry out drain piping Carry out drain piping so that drainage can be ensured Select the piping diameter equal to or larger than except for riser that...

Page 12: ...ot apply excessive force to the attached drain hose 1 by bending or twisting it This could cause water leakage In case of centralized drain piping carry out piping work according to the procedure show...

Page 13: ...terial 14 to perform the thermal insulation of the drain socket Do not connect the drain piping directly to the sewage that gives off ammonia odor The ammonia in the sewage may go through the drain pi...

Page 14: ...or insulate the wirings properly Insulation sleeve Ring type crimp style terminal Wiring Use the required wires connect and fix securely so that external force may not apply to the terminals Use a pr...

Page 15: ...pply wiring grounding wiring X2M Terminal block for remote controller wiring transmission wiring X1M Printed Circuit Board Forced off Remote controller wiring X1M Transmission wiring X1M Remote contro...

Page 16: ...1 system When using 1 remote controller Normal operation Indoor unit Power supply single phase 60Hz 208 230V Outdoor unit Remote controller L1L2 IN D OUT D F1 F2 F1 F2 P1 P2 P1 P2 F1 F2 T1 T2 Control...

Page 17: ...If test operation is carried out before mounting the decora tion panel check the horizontal blade action after the panel is mounted 9 FIELD SETTING Refer to also the installation manual attached to th...

Page 18: ...Differential MODE NO FIRST CODE NO SECOND CODE NO 1 8 F 1 C 12 22 2 01 0 9 F 0 5 C 02 9 7 SETTING AIR DISCHARGE DIRECTION When changing air discharge setting 2 way or 3 way air discharge set the SECON...

Page 19: ...the air conditioner until the interior finish work is completed If the air conditioner is operated the inside of the indoor units may be polluted by substances generated from the coating and adhesives...

Page 20: ...2209 HT 3P693452 2 EM21A045 Daikin Texas Technology Park 19001 Kermier Road Waller TX 77484 U S A 00_CV_3P693452 2 indd 2 2022 07 07 16 49 30...

Reviews: