background image

EWAP110~340MBYNN

Packaged air-cooled water chillers

4PW22677-1

Operation manual

4

2

Circuit safety devices

Circuit safety devices shut down the circuit they protect. For this
reason the unit does not need to be manually put on again after
a circuit safety occurred.

3

Part safety devices

Part safety devices shut down the part they protect.

An overview of all safety devices is given below.

Overcurrent relay
The overcurrent relays (K*S) are located in the switchbox of the
unit and protect the compressor motors in case of overload,
phase failure or too low voltage. The relays are factory-set and
may not be adjusted. When activated, they must be reset
manually, followed by a reset of the controller.

Compressor thermal protectors
The compressor motors are equipped with thermal protectors
(Q*M). The protectors are activated when the compressor motor
temperature becomes too high.
When temperature returns to normal, the protectors reset
automatically, but the controller needs to be reset manually.

Fan motor thermal protector
The condenser fan motors are equipped with thermal protectors
(Q*F). The protectors are activated when the temperature
becomes too high. When temperature returns to normal, the
protectors reset automatically.

Flowswitch
The unit is protected by a flowswitch (S8L).
When the waterflow becomes lower than the minimum allowed
waterflow, the flowswitch shuts down the unit. When the
waterflow becomes normal, the protection resets automatically
but the controller still needs to be reset manually.

Discharge thermal protectors
The unit is equipped with discharge thermal protectors (S*T).
The protectors are activated when the temperature of the
refrigerant leaving the compressor becomes too high. When the
temperature returns to normal the protector resets automatically
and the controller needs to be reset manually.

Freeze-up protection
The freeze-up protection prevents the water in the evaporator
from freezing during operation. When the outlet water
temperature is too low, the controller disables the unit. When the
outlet water temperature returns to normal, the unit can start up
again.
When freeze-up protection occurs several times in a certain
period, the freeze-up alarm will be activated and the unit will be
shut down. The cause of freezing up should be investigated and
after outlet water temperature has risen enough, the alarm
indicator on the controller needs to be reset manually.

Low pressure safety
When the suction pressure of a circuit is too low, the circuit
controller shuts down the circuit. When the pressure returns to
normal, the safety device can be reset on the controller.

Pressure relief safety valve
The safety valve is activated when the pressure in the refrigerant
circuit becomes too high. If this occurs, shut down the unit and
contact your local dealer.

High pressure switch
Each circuit is protected by two high pressure switches (S*PH)
which measure the condenser pressure (pressure at the outlet
of the compressor). They are installed in the compressor
housing of the circuit. When the pressure becomes too high, the
pressure switches are activated and the circuit stops.
The switches are factory-set and may not be adjusted. When
activated, they must be reset by means of a screwdriver. The
controller still needs to be reset.

Reverse phase protector
The reverse phase protectors (R*P) prevent the screw
compressors from running in the wrong direction. If the
compressors do not start, two phases of the power supply must
be inverted.

Internal wiring - Parts table

Refer to the internal wiring diagram supplied with the unit. The
abbreviations used are listed below:

A1............... **........ Current transfo/A-meter

A1P ........................ PCB controller

B1P ........................ Low pressure transmitter

B2P ........................ High pressure transmitter

C1~C3.................... Capacitor

E1HC ..................... Crankcase heater compressor

E3H ........................ Evaporator heater

F1U~F3U ... #......... Main fuses

F4U,F5U .... #......... Fuses for evaporator heater

F6B ........................ Fuse for primary of TR1

F7B ........................ Fuse for secondary of TR1

F8U ........................ Surge proof fuse for A1P

F9B ........................ Fuse for secondary of TR2

F12B,F14B............. Fuse for fanmotors

H1P ............ * ......... Indication lamp general operation

H2P ............ * ......... Indication lamp alarm

H3P ............ * ......... Indication lamp operation compressor

H5P ............ * ......... Changeable output

J1 ........................... Power supply

J2,J3,J6.................. Analog input

J5,J7,J8.................. Digital input

J11 ......................... RS485 connection

J12~J18 ................. Digital output

K1M........................ Linecontactor

K2M........................ Deltacontactor

K3M........................ Starcontactor

K7F~K9F................ Fancontactor

K17S ...................... Overcurrent relay

K1A ........................ Auxiliary relay for safeties

K2A ........................ Auxiliary relay compressor thermal protector

K3A ........................ Auxiliary relay for discharge thermal protector

K7A ........................ Auxiliary relay for safety of high pressure

L1~L3 ..................... Main supply terminals

M11F-M18F ........... Fan motors

M1C ....................... Compressor motor

M1S........................ Stepless capacity control for compressor

PE .......................... Main earth terminal

Q11F-Q18F............ Thermal protectors fan motors

Q1M ....................... Thermal protector compressor motor

R1 .......................... Auxiliary resistence for feedback (R1F)

R1F ........................ Feedback resistance

R1P ........................ Reverse phase protector

R3T ........................ Sensor for evaporator inlet water temperature

R4T ........................ Sensor for outlet water temperature

R5T ........................ Sensor for ambient temperature

R8T ........................ Sensor for evaporator outlet water temperature in 

a DICN system

S1PH...................... High pressure switch

S3T ........................ Discharge thermal protector

S5E ........................ Emergency stop push button

S6S ............ * ......... Changeable switch for remote function 

(e.g. remote start/stop)

Summary of Contents for EWAP110MBYNN

Page 1: ...OPERATION MANUAL EWAP110MBYNN EWAP140MBYNN EWAP160MBYNN EWAP200MBYNN EWAP280MBYNN EWAP340MBYNN Packaged air cooled water chillers...

Page 2: ...first time make sure that it has been properly installed It is therefore necessary to carefully read the installation manual supplied with the unit and the recommendations listed in Checks before ini...

Page 3: ...8 1 18 16 11 3 4 17 13 14 15 2 9 5 6 21 19 12 7 22 9 10 10 21 EWAP200 340 EWAP110 160 EWAP110 160 EWAP200 340 1 Evaporator 12 Power supply intake 2 Condenser 13 Emergency stop S5E 3 Compressor M1C 14...

Page 4: ...flows through it This is done by turning the liquid refrigerant coming from the condenser into gaseous refrigerant Water in outlet connection The water inlet and outlet connection allow an easy connec...

Page 5: ...e circuit controller shuts down the circuit When the pressure returns to normal the safety device can be reset on the controller Pressure relief safety valve The safety valve is activated when the pre...

Page 6: ...on oil leakage If there is an oil leak call your local dealer 10 Stop valves Open the liquid line discharge and suction if provided stop valves completely 11 Air inlet outlet Check that the air inlet...

Page 7: ...e specifications For units in a DICN configuration the remote digital controllers of the units can be installed at a distance of up to 50 metres by using a 6 ray telephone cable with a maximum cable r...

Page 8: ...d capacity of that specific circuit When a circuit is OFF the following status information may appear one of the circuit safety devices is activated refer to Troubleshooting on page 15 the circuit is...

Page 9: ...controller is activated When a network safety occurs in a DICN configuration the slaves not detected by the network will function as stand alone units If a slave unit can not be found by the network t...

Page 10: ...reen of the network menu To consult information about the unit status To consult information about the pressures To consult actual operational information about the ambient temperature the total runni...

Page 11: ...he moment of the unit shutdown To check which were the evaporator and condenser inlet water temperature and the evaporator outlet water temperature To check which was the status of the compressors at...

Page 12: ...e capacity limitation 1 the capacity limitation is not active capacity limitation value of circuit 1 in case of capacity limitation 1 2 3 4 Defining the pump control settings The screen of the user se...

Page 13: ...in the service menu Refer to the installation manual used to define the free cooling mode free cooling is not active free cooling is based on ambient temperature free cooling is based on the differen...

Page 14: ...he waterflow through the evaporator stops after the flowstart timer has reached zero If the waterflow has not restarted during the countdown the unit will shut down PUMPLEAD refer to the pump control...

Page 15: ...hich contains the following information the time and date 2 Press h to consult the first screen This screen contains information about the unit name and the refrigerant used 3 Press h to consult the n...

Page 16: ...ty devices may be bridged or changed to a value other than the factory setting If the cause of the problem cannot be found call your local dealer Symptom 1 The unit does not start but the ON LED light...

Page 17: ...sed electrician RESET After pressure decrease push the button on the high pressure switch and reset the controller Symptom 5 4 Fan thermal protector is activated POSSIBLE CAUSES CORRECTIVE ACTION Mech...

Page 18: ...r local dealer Water supply Check if the water connection is still well fixed Check the water quality refer to the installation manual of the unit for specifications of the water quality Water filters...

Page 19: ...in group 1 all Wednesdays will work according to the settings in group 2 all Saturdays and Sundays will work according to the settings in group 3 all holiday days will work according to the settings...

Page 20: ...tween inlet water evaporator temperature and ambient temperature Floating setpoint Default value Lower limit Upper limit Maximum value C 3 0 0 0 5 0 D1 C 20 0 20 0 43 0 D2 a a rise in floating setpoin...

Page 21: ...0 ANNEX V SOFTWARE STRUCTURE g 0 1 2 q h q q g h h h g h g g h g h g h g h g h g h g h g g h g h g h g h g h h h h h g g g 2 f 4 4 4 4 2 4 4 4 4 4 4 4 0 4 4 g h g h g h 2 2 2 2 q h h g q 6 h g h g h g...

Page 22: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PW22677 1...

Reviews: