background image

Operation manual

5

EWAP110~340MBYNN

Packaged air-cooled water chillers

4PW22677-1

S8L.........................Flowswitch

S9L............. # .........Contact that closes if the pump is working

S10S .......... * .........Changeable switch for remote function 

(e.g. dual setpoint)

S11S .......... * .........Changeable switch for remote function

(e.g. enable/disable capacity limitation 1)

S12S .......... * .........Changeable switch for remote function

(e.g. enable/disable capacity limitation 2)

S13S .......... ## .......Main isolator switch

S14PH....................High pressure switch

TC01,TC02.............Optocoupler (analog to digital signal)

TR1 ........................Transfo for control circuit

TR2 ........................Transfo for supply cont digital inputs

V1............... ** ........V-meter

Y11S ......................12% capacity step for compressor

Y15S ......................Liquid injection valve of the compressor

Y16S ......................Liquid line solenoid valve

B

EFORE

 

OPERATION

Checks before initial start-up

After the installation of the unit, check the following before switching
on the circuit breaker:

1

Field wiring

Make sure that the field wiring between the local supply panel
and the unit has been carried out according to the instructions
described in the installation manual, according to the wiring
diagrams and according to European and national regulations.

2

Additional pump interlock contact

Additional pump interlock contact (S9L) must be provided. Make
sure that the contact has been installed between the appropriate
terminals (refer to the wiring diagram supplied with the unit). The
contact must be a normal open contact.

3

Fuses or protection devices

Check that the fuses or the locally installed protection devices
are of the size and type specified in the installation manual.
Make sure that neither a fuse nor a protection device has been
bypassed.

4

Earth wiring

Make sure that the earth wires have been connected properly
and that the earth terminals are tightened.

5

Internal wiring

Visually check the switch box on loose connections or damaged
electrical components.

6

Fixation

Check that the unit is properly fixed, to avoid abnormal noises
and vibrations when starting up the unit.

7

Damaged equipment

Check the inside of the unit on damaged components or
squeezed pipes.

8

Refrigerant leak

Check the inside of the unit on refrigerant leakage. If there is a
refrigerant leak, call your local dealer.

9

Oil leak

Check the compressor on oil leakage. If there is an oil leak, call
your local dealer.

10

Stop valves

Open the liquid line, discharge and suction (if provided) stop
valves completely.

11

Air inlet/outlet

Check that the air inlet and outlet of the unit is not obstructed by
paper sheets, cardboard, or any other material.

12

Power supply voltage

Check the power supply voltage on the local supply panel. The
voltage must correspond to the voltage on the identification label
of the unit.

13

Water connection

Check water piping system and circulating pumps.
Check if the filter kit that was supplied with the unit separately is
installed correctly in front of the evaporator water inlet.

14

Water sensors

Check that all the water sensors are correctly fixed into the pipes
connected to the evaporator.

Water supply

Fill the water piping, taking into account the minimum water volume
required by the unit. Refer to the Installation manual.

Make sure that the water is of the quality as mentioned in the
installation manual.

Purge the air at the high points of the system and check the operation
of the circulation pump and the flowswitch.

Power supply connection and crankcase heating

To switch on the crankcase heater proceed as follows:

1

Switch on the circuit breaker on the local supply panel. Make
sure that the unit is "OFF".

2

The crankcase heater is switched on automatically.

3

Check the supply voltage on the supply terminals L1, L2, L3, by
means of a voltmeter. The voltage must correspond to the
voltage indicated on the identification label of the unit. If the
voltmeter reads values which are not within the ranges specified
in the technical data, check the field wiring and replace the
supply cables if necessary.

4

Check the LED on the reverse phase protectors. If it lights up,
the phase order is correct. If not, switch off the circuit breaker
and call a licensed electrician to connect the wires of the power
supply cable in the correct phase order.

5

Check if the crankcase heaters are warming up.

After 8 hours, the unit is ready for operation.

Not included with standard unit

Not possible as option

Possible as option

Obligatory

#

##

Not obligatory

*

**

Make sure that the circuit breaker on the power supply
panel of the unit is switched off.

In order to avoid compressor damage, it is necessary to
switch on the crankcase heater for at least 8 hours before
starting the compressor after a long period of standstill.

Summary of Contents for EWAP110MBYNN

Page 1: ...OPERATION MANUAL EWAP110MBYNN EWAP140MBYNN EWAP160MBYNN EWAP200MBYNN EWAP280MBYNN EWAP340MBYNN Packaged air cooled water chillers...

Page 2: ...first time make sure that it has been properly installed It is therefore necessary to carefully read the installation manual supplied with the unit and the recommendations listed in Checks before ini...

Page 3: ...8 1 18 16 11 3 4 17 13 14 15 2 9 5 6 21 19 12 7 22 9 10 10 21 EWAP200 340 EWAP110 160 EWAP110 160 EWAP200 340 1 Evaporator 12 Power supply intake 2 Condenser 13 Emergency stop S5E 3 Compressor M1C 14...

Page 4: ...flows through it This is done by turning the liquid refrigerant coming from the condenser into gaseous refrigerant Water in outlet connection The water inlet and outlet connection allow an easy connec...

Page 5: ...e circuit controller shuts down the circuit When the pressure returns to normal the safety device can be reset on the controller Pressure relief safety valve The safety valve is activated when the pre...

Page 6: ...on oil leakage If there is an oil leak call your local dealer 10 Stop valves Open the liquid line discharge and suction if provided stop valves completely 11 Air inlet outlet Check that the air inlet...

Page 7: ...e specifications For units in a DICN configuration the remote digital controllers of the units can be installed at a distance of up to 50 metres by using a 6 ray telephone cable with a maximum cable r...

Page 8: ...d capacity of that specific circuit When a circuit is OFF the following status information may appear one of the circuit safety devices is activated refer to Troubleshooting on page 15 the circuit is...

Page 9: ...controller is activated When a network safety occurs in a DICN configuration the slaves not detected by the network will function as stand alone units If a slave unit can not be found by the network t...

Page 10: ...reen of the network menu To consult information about the unit status To consult information about the pressures To consult actual operational information about the ambient temperature the total runni...

Page 11: ...he moment of the unit shutdown To check which were the evaporator and condenser inlet water temperature and the evaporator outlet water temperature To check which was the status of the compressors at...

Page 12: ...e capacity limitation 1 the capacity limitation is not active capacity limitation value of circuit 1 in case of capacity limitation 1 2 3 4 Defining the pump control settings The screen of the user se...

Page 13: ...in the service menu Refer to the installation manual used to define the free cooling mode free cooling is not active free cooling is based on ambient temperature free cooling is based on the differen...

Page 14: ...he waterflow through the evaporator stops after the flowstart timer has reached zero If the waterflow has not restarted during the countdown the unit will shut down PUMPLEAD refer to the pump control...

Page 15: ...hich contains the following information the time and date 2 Press h to consult the first screen This screen contains information about the unit name and the refrigerant used 3 Press h to consult the n...

Page 16: ...ty devices may be bridged or changed to a value other than the factory setting If the cause of the problem cannot be found call your local dealer Symptom 1 The unit does not start but the ON LED light...

Page 17: ...sed electrician RESET After pressure decrease push the button on the high pressure switch and reset the controller Symptom 5 4 Fan thermal protector is activated POSSIBLE CAUSES CORRECTIVE ACTION Mech...

Page 18: ...r local dealer Water supply Check if the water connection is still well fixed Check the water quality refer to the installation manual of the unit for specifications of the water quality Water filters...

Page 19: ...in group 1 all Wednesdays will work according to the settings in group 2 all Saturdays and Sundays will work according to the settings in group 3 all holiday days will work according to the settings...

Page 20: ...tween inlet water evaporator temperature and ambient temperature Floating setpoint Default value Lower limit Upper limit Maximum value C 3 0 0 0 5 0 D1 C 20 0 20 0 43 0 D2 a a rise in floating setpoin...

Page 21: ...0 ANNEX V SOFTWARE STRUCTURE g 0 1 2 q h q q g h h h g h g g h g h g h g h g h g h g h g g h g h g h g h g h h h h h g g g 2 f 4 4 4 4 2 4 4 4 4 4 4 4 0 4 4 g h g h g h 2 2 2 2 q h h g q 6 h g h g h g...

Page 22: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PW22677 1...

Reviews: