background image

EWAP110~340MBYNN

Packaged air-cooled water chillers

4PW22677-1

Operation manual

14

Tasks of the safeties menu

Listing activated safeties and checking the unit status

If the alarm buzzer is activated and the user presses the 

p

 key, the

controller automatically enters the safeties menu.

The controller will enter the 

 

 screen of the safeties

menu when a unit safety was the cause of shutdown.

The controller will enter the 

 

 screen of the

safeties menu when a safety of the circuit was activated.

For a DICN system, the controller can also show: 

    &  

. This occurs when the wrong

number of slave units is defined (refer to 

"Defining the network

settings" on page 12

) or when a slave unit is missing (because

of bad connection or power supply failure).
Make sure to define the correct number of slave units and to
make correct connections.

When the unit is configured with a dual evaporator pump, the
controller will enter the 

   

  screen of the

safeties menu when a safety on the pump was the cause of
shutdown.

1

Press the 

p

 key when the alarm buzzer is activated.

The appropriate safety screen with the basic information
appears. Press the 

q

 key to see the detailed information. These

screens provide information about the unit status at the moment
of shutdown (see 

"Safeties menu" on page 10

).

2

If more than one kind of safety is active (indicated by means of

W

X

 or 

C

), use the 

and

 h

 keys to consult them.

Tasks of the history menu

Checking the safety info and the unit status after a reset

The information available in the safeties menu is also stored in the
history menu, where it is stored after resetting the unit or the circuit.
In this way, the history menu provides a means of checking the unit
status at the moment of the latest shutdown.

To check the safety info and the unit status, proceed as follows:

1

Enter the 

 

. (Refer to the chapter 

"How to enter a

menu" on page 6

.)

The controller enters the last 

  screen which contains

basic information of the moment of this shutdown.

2

Press the 

and

 h

 keys to consult the other present 

screens.

3

Press the 

q

 key to see the detailed information.

Tasks of the info menu

Consulting additional unit information

1

Enter the 

   

through the main menu. (Refer to the

chapter 

"How to enter a menu" on page 6

).

The controller enters the 

   

  screen which

contains the following information: the time and date.

2

Press 

h

 to consult the first 

 

 screen.

This screen contains information about the unit name and the
refrigerant used.

3

Press 

h

 to consult the next 

 

 screen.

This screen contains information about the controller's software
version.

4

Press 

h

 to consult the 

 

 screen.

This screen contains information about the PCB.

Tasks of the input/output menu

Checking the status of the inputs and outputs

The input/output menu provides a means of checking the status of
the digital inputs and the status of the relay outputs.

The locked digital inputs are:

 

:  whether the emergency button has been

pressed.

: indicates the status of the flowswitch: activated or

deactivated.

   

: indicates the actual status of this

safety.

   

: indicates the actual status of

this safety.

 

: indicates the actual status of this safety.

   

:  indicates the actual

status of this safety.

     

:  indicates the actual

status of this safety.

The changeable digital inputs are:

   "#

: indicates the position of the "enable/disable

capacity limitation" switches.

 

:  indicates the position of the remote dual

setpoint switch: setpoint 1 or setpoint 2.

 &

: indicates the position of the remote on/off switch.

: indicates the position of the connected switch.

The locked relay outputs are:

 

: indicates whether the circuit is on or off.

 

: indicates whether the circuit is in starmode

or not.

 

: indicates whether the circuit is in deltamode

or not.

 *

:  indicates if the 12% capacity valve of the circuit is

activated.

 

: indicates if the 

 of the capacity control motor of the

circuit is activated.

 

: indicates if the 

 of the capacity control motor of

the circuit is activated.

 

: indicates the 

 of the potentiometer of

the circuit (

).

 

: indicates if the fans of fanstep 1 for the circuit

are on or not.

 

: indicates if the fans of fanstep 2 for the circuit

are on or not.

  "

: indicates if the fans of fanstep 3 for the circuit

are on or not.

 

: indicates the status of this voltage free contact. It

is activated if the pump should be ON.

&  

: indicates the status of this voltage free contact. It

is activated if there is any alarm on the unit.

&

: indicates the status of the evaporator heater.

The changeable relay outputs are:

   

: indicates the status of the second evaporator

pump.

%%*

: indicates when the unit is working at 100%.

 

:  indicates the status of the 3-way water valve

when the unit is in free cooling state.

 

:  indicates the closed status of the changeable

digital output.

NOTE

You can check the "found" slave units in the 2nd
screen of the network menu.

Summary of Contents for EWAP110MBYNN

Page 1: ...OPERATION MANUAL EWAP110MBYNN EWAP140MBYNN EWAP160MBYNN EWAP200MBYNN EWAP280MBYNN EWAP340MBYNN Packaged air cooled water chillers...

Page 2: ...first time make sure that it has been properly installed It is therefore necessary to carefully read the installation manual supplied with the unit and the recommendations listed in Checks before ini...

Page 3: ...8 1 18 16 11 3 4 17 13 14 15 2 9 5 6 21 19 12 7 22 9 10 10 21 EWAP200 340 EWAP110 160 EWAP110 160 EWAP200 340 1 Evaporator 12 Power supply intake 2 Condenser 13 Emergency stop S5E 3 Compressor M1C 14...

Page 4: ...flows through it This is done by turning the liquid refrigerant coming from the condenser into gaseous refrigerant Water in outlet connection The water inlet and outlet connection allow an easy connec...

Page 5: ...e circuit controller shuts down the circuit When the pressure returns to normal the safety device can be reset on the controller Pressure relief safety valve The safety valve is activated when the pre...

Page 6: ...on oil leakage If there is an oil leak call your local dealer 10 Stop valves Open the liquid line discharge and suction if provided stop valves completely 11 Air inlet outlet Check that the air inlet...

Page 7: ...e specifications For units in a DICN configuration the remote digital controllers of the units can be installed at a distance of up to 50 metres by using a 6 ray telephone cable with a maximum cable r...

Page 8: ...d capacity of that specific circuit When a circuit is OFF the following status information may appear one of the circuit safety devices is activated refer to Troubleshooting on page 15 the circuit is...

Page 9: ...controller is activated When a network safety occurs in a DICN configuration the slaves not detected by the network will function as stand alone units If a slave unit can not be found by the network t...

Page 10: ...reen of the network menu To consult information about the unit status To consult information about the pressures To consult actual operational information about the ambient temperature the total runni...

Page 11: ...he moment of the unit shutdown To check which were the evaporator and condenser inlet water temperature and the evaporator outlet water temperature To check which was the status of the compressors at...

Page 12: ...e capacity limitation 1 the capacity limitation is not active capacity limitation value of circuit 1 in case of capacity limitation 1 2 3 4 Defining the pump control settings The screen of the user se...

Page 13: ...in the service menu Refer to the installation manual used to define the free cooling mode free cooling is not active free cooling is based on ambient temperature free cooling is based on the differen...

Page 14: ...he waterflow through the evaporator stops after the flowstart timer has reached zero If the waterflow has not restarted during the countdown the unit will shut down PUMPLEAD refer to the pump control...

Page 15: ...hich contains the following information the time and date 2 Press h to consult the first screen This screen contains information about the unit name and the refrigerant used 3 Press h to consult the n...

Page 16: ...ty devices may be bridged or changed to a value other than the factory setting If the cause of the problem cannot be found call your local dealer Symptom 1 The unit does not start but the ON LED light...

Page 17: ...sed electrician RESET After pressure decrease push the button on the high pressure switch and reset the controller Symptom 5 4 Fan thermal protector is activated POSSIBLE CAUSES CORRECTIVE ACTION Mech...

Page 18: ...r local dealer Water supply Check if the water connection is still well fixed Check the water quality refer to the installation manual of the unit for specifications of the water quality Water filters...

Page 19: ...in group 1 all Wednesdays will work according to the settings in group 2 all Saturdays and Sundays will work according to the settings in group 3 all holiday days will work according to the settings...

Page 20: ...tween inlet water evaporator temperature and ambient temperature Floating setpoint Default value Lower limit Upper limit Maximum value C 3 0 0 0 5 0 D1 C 20 0 20 0 43 0 D2 a a rise in floating setpoin...

Page 21: ...0 ANNEX V SOFTWARE STRUCTURE g 0 1 2 q h q q g h h h g h g g h g h g h g h g h g h g h g g h g h g h g h g h h h h h g g g 2 f 4 4 4 4 2 4 4 4 4 4 4 4 0 4 4 g h g h g h 2 2 2 2 q h h g q 6 h g h g h g...

Page 22: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PW22677 1...

Reviews: