background image

Operation manual

13

EWAP110~340MBYNN

Packaged air-cooled water chillers

4PW22677-1

:  The 

  time defines the target difference in

running hours between one unit and another unit with

%%%% 2

.  This value is important for maintenance

purposes. The difference in setting among different units should
be high enough as to avoid servicing of the units all at the same
time. The lower and upper limits are 0 and 9000 hours
respectively. The default value is 0 hours.

   

: Set if the pump must operate as long as the chiller

is on (

 

), or during compressor on condition only (

 

).

When 

 

  is selected, the voltage free contact S9L will

remain closed as long as the chiller is on. When 

 

  is

selected, the voltage free contact S9L will remain closed as long
as the compressor is on.
Also refer to the separate manual "Installation examples for a
DICN configuration".

Activating or deactivating the setpoints password

The 

 

 screen of the user settings menu allows

the user to activate or deactivate the user password needed to
change the temperature setpoint. When deactivated, the user does
not have to enter the password each time he wants to change the
setpoint.

Defining BMS control

 

 allows the user to control the unit from a supervisory system.

The 

 

 screen and 

 

 screen of the

service menu have to be used to set BMS parameters. Refer to
"Customization in the service menu" chapter "Defining the BMS
settings" in the installation manual.

Tasks of the timers menu

Checking the actual value of the software timers

As a protective measure and to ensure correct operation, the
controller's software features several countdown timers:

LOADUP (

 – refer to the thermostat parameters): starts

counting when a thermostat step change has occurred. During
the countdown, the unit is not able to enter a higher thermostat
step.

LOADDOWN (

 – refer to the thermostat parameters): starts

counting when a thermostat step change has occurred. During
the countdown, the unit will not be able to go to a lower
thermostat step.

FLOWSTART (

  – 15 sec): counts down when the

waterflow through the evaporator is continuous and the unit is in
standby. During the countdown, the unit cannot start up.

FLOWSTOP (

  – 5 sec): starts counting when the

waterflow through the evaporator stops after the flowstart timer
has reached zero. If the waterflow has not restarted during the
countdown, the unit will shut down.

PUMPLEAD (

 

  – refer to the pump control settings):

starts counting whenever the unit is switched on. During the
countdown, the unit cannot start up.

PUMPLAG (

 

  – refer to the pump control settings):

starts counting whenever the unit is switched off. During the
countdown, the pump keeps running.

STARTTIMER (

 &

  – 10 sec): starts counting

whenever a compressor starts up. During the countdown, no
other compressor can start up.

GUARDTIMER (

  – 60 sec): starts counting when the

compressor has been shut down. During the countdown, the
compressor cannot be restarted.

ANTIRECYCLING (

 – 600 sec): starts counting when the

compressor has started. During the countdown, the compressor
cannot be restarted.

STARTUPTIMER (

 

  – 180 sec): starts counting

when the compressor has started. During the countdown, the
compressor is limited to a maximum capacitystep of 30%.

To check the actual value of the software timers, proceed as follows:

1

Enter the 

   

. (Refer to the chapter 

"How to enter a

menu" on page 6

.)

The controller displays the actual value of the 

 

:  the loadup timer, the loaddown timer, the flowstart

timer, the flowstop timer (when the unit is on and the flowstart
timer has reached zero), the pumplead timer and the pumplag
timer.

2

Press the 

h

 key to check the compressor timers.

The controller shows the actual value of the 

 

 

: the guard timers (one per circuit) and the antirecycling

timers (one per circuit).

3

Press the 

h

 key to check the remaining timers.

The controller shows the actual value of the 

 

.

NOTE

Put a unit to 

  

when servicing the

machine. In this case it is possible to switch ON or
OFF this unit without switching ON or OFF the other
units of the network.

It is also possible then to operate the unit in 

 

.

Put a unit to 

  

continuously if the

operator wants to decide by himself when this unit
must operate.

Note that in this case, it makes no sense to define
another unit of the network as 

. Since there is

a unit set continuously to 

 

, the

  unit will continuously be considered as a

 

 unit.

NOTE

The settings on this screen of the network menu must
be executed for all chillers connected to the system.

NOTE

If changed on one of the units in a DICN configuration,
this setting is automatically transferred to all the other
units in the network.

Summary of Contents for EWAP110MBYNN

Page 1: ...OPERATION MANUAL EWAP110MBYNN EWAP140MBYNN EWAP160MBYNN EWAP200MBYNN EWAP280MBYNN EWAP340MBYNN Packaged air cooled water chillers...

Page 2: ...first time make sure that it has been properly installed It is therefore necessary to carefully read the installation manual supplied with the unit and the recommendations listed in Checks before ini...

Page 3: ...8 1 18 16 11 3 4 17 13 14 15 2 9 5 6 21 19 12 7 22 9 10 10 21 EWAP200 340 EWAP110 160 EWAP110 160 EWAP200 340 1 Evaporator 12 Power supply intake 2 Condenser 13 Emergency stop S5E 3 Compressor M1C 14...

Page 4: ...flows through it This is done by turning the liquid refrigerant coming from the condenser into gaseous refrigerant Water in outlet connection The water inlet and outlet connection allow an easy connec...

Page 5: ...e circuit controller shuts down the circuit When the pressure returns to normal the safety device can be reset on the controller Pressure relief safety valve The safety valve is activated when the pre...

Page 6: ...on oil leakage If there is an oil leak call your local dealer 10 Stop valves Open the liquid line discharge and suction if provided stop valves completely 11 Air inlet outlet Check that the air inlet...

Page 7: ...e specifications For units in a DICN configuration the remote digital controllers of the units can be installed at a distance of up to 50 metres by using a 6 ray telephone cable with a maximum cable r...

Page 8: ...d capacity of that specific circuit When a circuit is OFF the following status information may appear one of the circuit safety devices is activated refer to Troubleshooting on page 15 the circuit is...

Page 9: ...controller is activated When a network safety occurs in a DICN configuration the slaves not detected by the network will function as stand alone units If a slave unit can not be found by the network t...

Page 10: ...reen of the network menu To consult information about the unit status To consult information about the pressures To consult actual operational information about the ambient temperature the total runni...

Page 11: ...he moment of the unit shutdown To check which were the evaporator and condenser inlet water temperature and the evaporator outlet water temperature To check which was the status of the compressors at...

Page 12: ...e capacity limitation 1 the capacity limitation is not active capacity limitation value of circuit 1 in case of capacity limitation 1 2 3 4 Defining the pump control settings The screen of the user se...

Page 13: ...in the service menu Refer to the installation manual used to define the free cooling mode free cooling is not active free cooling is based on ambient temperature free cooling is based on the differen...

Page 14: ...he waterflow through the evaporator stops after the flowstart timer has reached zero If the waterflow has not restarted during the countdown the unit will shut down PUMPLEAD refer to the pump control...

Page 15: ...hich contains the following information the time and date 2 Press h to consult the first screen This screen contains information about the unit name and the refrigerant used 3 Press h to consult the n...

Page 16: ...ty devices may be bridged or changed to a value other than the factory setting If the cause of the problem cannot be found call your local dealer Symptom 1 The unit does not start but the ON LED light...

Page 17: ...sed electrician RESET After pressure decrease push the button on the high pressure switch and reset the controller Symptom 5 4 Fan thermal protector is activated POSSIBLE CAUSES CORRECTIVE ACTION Mech...

Page 18: ...r local dealer Water supply Check if the water connection is still well fixed Check the water quality refer to the installation manual of the unit for specifications of the water quality Water filters...

Page 19: ...in group 1 all Wednesdays will work according to the settings in group 2 all Saturdays and Sundays will work according to the settings in group 3 all holiday days will work according to the settings...

Page 20: ...tween inlet water evaporator temperature and ambient temperature Floating setpoint Default value Lower limit Upper limit Maximum value C 3 0 0 0 5 0 D1 C 20 0 20 0 43 0 D2 a a rise in floating setpoin...

Page 21: ...0 ANNEX V SOFTWARE STRUCTURE g 0 1 2 q h q q g h h h g h g g h g h g h g h g h g h g h g g h g h g h g h g h h h h h g g g 2 f 4 4 4 4 2 4 4 4 4 4 4 4 0 4 4 g h g h g h 2 2 2 2 q h h g q 6 h g h g h g...

Page 22: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PW22677 1...

Reviews: