EWAP110~340MBYNN

Packaged air-cooled water chillers

4PW22677-1

Operation manual

12

Beside these four groups there is also a holiday period group
which is set the same way as the other groups. Up to 12 holiday
periods can be entered in the 

 

 screen. During these

periods the schedule timer will follow the settings of the holiday
period group.

Defining dual evaporator pump control

The 

 &  

 screen of the user settings menu allows the

user to define the steering of two evaporator pumps (for this to be
possible a changeable digital output has to be configured for a
second evaporator pump in the service menu). Refer to the
installation manual.

 

:  used to define which kind of control will be used for the

two evaporator pumps. When automatic rotation is chosen the
offset on running hours also has to be entered.

: pump 1 and pump 2 will alternate to the offset on RH.

   

: pump 1 will always start up first.

   

: pump 2 will always start up first.

 

:  used to define the offset in running hours

between the two pumps. Used to switch over between pumps
when they work in automatic rotation mode.

Defining the floating setpoint settings

The 

 

 screen of the user settings menu allows

the active setpoint to be modified in function of the ambient. The
source and settings of the floating setpoint can be configured by the
user.

: used to define the mode of the floating setpoint.

 

: floating setpoint is not activated.

 

:  floating setpoint is altered based on the ambient

temperature.

 1&

: used to define maximum value that can be added

to the active setpoint.

:  used to define the ambient (source) at which the floating

setpoint value is equal to zero.

:  used to define the rise in floating setpoint value for 10°C

drop in ambient.

Defining the display settings

The 

 

  screens of the usersettings menu allows

the user to define the choice of language, time and date.

:  used to define the language of the displayed

information of the controller (on the first screen). (Push the 

q

button repeatedly to change the operating language).

 

: used to define the present time (on the second screen).

: used to define the present date (on the second screen).

Defining free cooling

The 

 

 screen of the usersettings menu allows the user

to control a 3-way water valve when the unit is in free cooling state.
To  make this possible a changeable digital output has to be
configured for free cooling in the service menu. (Refer to the
installation manual.)

 

: used to define the free cooling mode.

 

: free cooling is not active.

 

: free cooling is based on ambient temperature.

 

:  free cooling is based on the difference

between inlet water temperature and ambient temperature.

: setting of the free cooling setpoint.

: setting of the free cooling difference.

Defining the network settings

The 

  screen of the user settings menu allows the user to

define the network settings.

 

: Define the number of slaves connected to the

master (1 to 3). This menu can only be accessed at the "Master"
unit.

The 

 screen of the network menu allows the user to set the

 

 of the unit, the 

 time and the condition when the pump

must operate.

 

:  Define the mode of the unit as 

 

  or

 

.

 

:  The unit is controlled by the network. Loading and

unloading is decided by the central control of the netwerk. Putting
this unit ON or OFF will also put all other units ON or OFF, unless
their status is 

 

. (see further)

Changing 

 

 or 

 

 to

this unit, will apply to all other units. 

 

 on such

a unit is not possible. Refer to 

"Defining and activating the control

mode" on page 11

.

:  The unit is considered as a 

 

  unit and its

function is then also simular to a unit defined as 

 

, but this

unit however, will only come into operation if:
another unit is in alarm
another unit is in 

  

mode

the setpoint is not reached when all other units have been
running on full capacity for some time
If more than one unit is defined as 

, only 1 of the units

will be really standby. The unit which is really standby will be
decided by the number of running hours.

 

: Putting this unit ON or OFF will not put

other units ON or OFF. 

 

  on such a unit is

possible.
If the unit is put to 

 

, and the unit is ON, it

will be controlled by the DICN network as a 

 

 unit.

NOTE

A functional diagram showing the schedule timer
working can be found in 

"Annex II" on page 18

.

NOTE

The unit always works with "last command". This
means that the last command given, whether manually
by  the user or by the schedule timer, is always
executed.

Examples of command that can be given are switching
the unit on/off or changing a setpoint.

NOTE

In case of a DICN network, defining the schedule timer
will only be possible through the master unit. In case of
power failure of the master unit, the slave units
however, will still operate according to settings of the
schedule timer.

NOTE

A functional diagram showing the floating setpoint
working can be found in 

"Annex III" on page 19

.

NOTE

A functional diagram showing the free cooling working
can be found in 

"Annex IV" on page 19

.

Summary of Contents for EWAP110MBYNN

Page 1: ...OPERATION MANUAL EWAP110MBYNN EWAP140MBYNN EWAP160MBYNN EWAP200MBYNN EWAP280MBYNN EWAP340MBYNN Packaged air cooled water chillers...

Page 2: ...first time make sure that it has been properly installed It is therefore necessary to carefully read the installation manual supplied with the unit and the recommendations listed in Checks before ini...

Page 3: ...8 1 18 16 11 3 4 17 13 14 15 2 9 5 6 21 19 12 7 22 9 10 10 21 EWAP200 340 EWAP110 160 EWAP110 160 EWAP200 340 1 Evaporator 12 Power supply intake 2 Condenser 13 Emergency stop S5E 3 Compressor M1C 14...

Page 4: ...flows through it This is done by turning the liquid refrigerant coming from the condenser into gaseous refrigerant Water in outlet connection The water inlet and outlet connection allow an easy connec...

Page 5: ...e circuit controller shuts down the circuit When the pressure returns to normal the safety device can be reset on the controller Pressure relief safety valve The safety valve is activated when the pre...

Page 6: ...on oil leakage If there is an oil leak call your local dealer 10 Stop valves Open the liquid line discharge and suction if provided stop valves completely 11 Air inlet outlet Check that the air inlet...

Page 7: ...e specifications For units in a DICN configuration the remote digital controllers of the units can be installed at a distance of up to 50 metres by using a 6 ray telephone cable with a maximum cable r...

Page 8: ...d capacity of that specific circuit When a circuit is OFF the following status information may appear one of the circuit safety devices is activated refer to Troubleshooting on page 15 the circuit is...

Page 9: ...controller is activated When a network safety occurs in a DICN configuration the slaves not detected by the network will function as stand alone units If a slave unit can not be found by the network t...

Page 10: ...reen of the network menu To consult information about the unit status To consult information about the pressures To consult actual operational information about the ambient temperature the total runni...

Page 11: ...he moment of the unit shutdown To check which were the evaporator and condenser inlet water temperature and the evaporator outlet water temperature To check which was the status of the compressors at...

Page 12: ...e capacity limitation 1 the capacity limitation is not active capacity limitation value of circuit 1 in case of capacity limitation 1 2 3 4 Defining the pump control settings The screen of the user se...

Page 13: ...in the service menu Refer to the installation manual used to define the free cooling mode free cooling is not active free cooling is based on ambient temperature free cooling is based on the differen...

Page 14: ...he waterflow through the evaporator stops after the flowstart timer has reached zero If the waterflow has not restarted during the countdown the unit will shut down PUMPLEAD refer to the pump control...

Page 15: ...hich contains the following information the time and date 2 Press h to consult the first screen This screen contains information about the unit name and the refrigerant used 3 Press h to consult the n...

Page 16: ...ty devices may be bridged or changed to a value other than the factory setting If the cause of the problem cannot be found call your local dealer Symptom 1 The unit does not start but the ON LED light...

Page 17: ...sed electrician RESET After pressure decrease push the button on the high pressure switch and reset the controller Symptom 5 4 Fan thermal protector is activated POSSIBLE CAUSES CORRECTIVE ACTION Mech...

Page 18: ...r local dealer Water supply Check if the water connection is still well fixed Check the water quality refer to the installation manual of the unit for specifications of the water quality Water filters...

Page 19: ...in group 1 all Wednesdays will work according to the settings in group 2 all Saturdays and Sundays will work according to the settings in group 3 all holiday days will work according to the settings...

Page 20: ...tween inlet water evaporator temperature and ambient temperature Floating setpoint Default value Lower limit Upper limit Maximum value C 3 0 0 0 5 0 D1 C 20 0 20 0 43 0 D2 a a rise in floating setpoin...

Page 21: ...0 ANNEX V SOFTWARE STRUCTURE g 0 1 2 q h q q g h h h g h g g h g h g h g h g h g h g h g g h g h g h g h g h h h h h g g g 2 f 4 4 4 4 2 4 4 4 4 4 4 4 0 4 4 g h g h g h 2 2 2 2 q h h g q 6 h g h g h g...

Page 22: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PW22677 1...