background image

Operation manual

7

EWAP110~340MBYNN

Packaged air-cooled water chillers

4PW22677-1

Setting the language

If desired, the operating language can be changed to any of the
following languages: English, German, French, Spanish or Italian.

1

Enter the usersettings menu. Refer to chapter 

"How to enter a

menu" on page 6

2

Go to the appropriate screen of the usersettings menu using the

and

 h

 keys.

3

Press 

q

  to change the operating language until the desired

language is active.

Switching the unit on

1

Press the 

J

 key on the controller.

Depending on wheter or not a remote ON/OFF switch has been
configured (

refer to the installation manual

), the following

conditions may occur.
When no remote ON/OFF switch is configured, the LED inside
the 

J

 key lights up and an initialization cycle is started. Once all

the timers have reached zero, the unit starts up.
When a remote ON/OFF switch is configured, the following table
applies:

2

If the water chiller does not start after a few minutes, refer to

"Troubleshooting" on page 15

.

Switching the unit off

If no remote on/off switch is configured:

Press the 

o

 key on the controller.

The LED inside the 

o

 key goes out.

If a remote on/off switch is configured:

Press the 

o

 key on the controller or switch the unit off using the

remote on/off switch.
The LED inside the 

o

 key goes out in the first case and starts

blinking in the second case.

Switching units ON/OFF in a DICN system

If the 

o

 key is pressed on a unit with status 

 

 or 

, all

other units with status 

 

 or 

 will be ON or OFF.

If the 

o

 key is pressed on a unit with status 

 

,

only this unit will be ON or OFF.

Consulting actual operational information

1

Enter the readout menu. Refer to the chapter 

"How to enter a

menu" on page 6

.

The controller automatically shows the first screen of the
readout menu which provides the following information:

   

  or 

  or 

:  manual/

automatic control mode operation. If the automatic control mode
is selected, the controller will indicate the active temperature
setpoint. Depending on the status of the remote contact, setpoint
one or setpoint two is active.

 

: actual evaporator inlet water temperature.

 

: actual evaporator outlet water temperature.

2

Press the 

h

 key to enter the next screen of the readout menu.

The 

 

  screen of the readout menu provides

information concerning the status of the different circuits.

: actual status of circuit.

When the circuit is ON, the following status information may
appear.

: 40% - this percentage refers to the activated capacity of that

specific circuit.

When a circuit is OFF, the following status information may
appear.

 

:  one of the circuit safety devices is activated

(refer to 

"Troubleshooting" on page 15

).

 

: the circuit is limited by a remote contact.

 

: the actual value of one of the software timers is

not zero (refer to 

"Timers menu" on page 9

).

 

 the circuit is ready to start up when extra cooling

load is needed.

The preceding OFF messages are written down in order of priority. If
one of the timers is busy and one of the safeties is active, the status
information says 

 

.

The 

 

  is written down on the bottom of the screen.

The percentage is the actual cooling capacity of the unit.

3

Press the 

h

 key to enter the next screen of the readout menu.

The 

 

 screen of the readout menu provides

information concerning the pressures of circuit.

:  high pressure of the refrigerant in circuit. The first

number stands for the pressure in bar, the second number
stands for the bubble point saturation temperature in degrees
Celsius.

:  low pressure of the refrigerant in circuit. The first

number stands for the pressure in bar, the second number
stands for the dew point saturation temperature in degrees
Celsius.

Local key

Remote switch

Unit

o

o

o

o

 LED

ON

ON

ON

ON

ON

OFF

OFF

Flashing

OFF

ON

OFF

OFF

OFF

OFF

OFF

OFF

In case of emergency, switch off the unit by pushing the
emergency stopbutton.

NOTE

Also consult 

"Defining the schedule timer" on page 11

and "Customization in the service menu" chapter
"Setting of the changeable inputs and outputs" in the
installation manual.

NOTE

When a remote ON/OFF switch is configured, the
remote ON/OFF contact for all units with status

 

 or 

 of a DICN network is the contact

connected to the master unit.

For units with status 

 

, the remote

contact is the contact connected to this unit.

NOTE

If the user wants 1 unit to operate on his command
only, this unit is to be set to 

 

.

It is recommended not to select the master unit for this
purpose. Even if the status of the master is set to

 

, it will still be the contact

connected to the master which will switch ON/OFF the
other units in 

 

  or 

  mode. It would

therefore never be possible to only switch the master
unit OFF remotely.

Switching OFF the master unit only, should in this case
be done by the local ON/OFF key on the master unit.

NOTE

For a DICN system, the 

 

 values are the values of the individual units, not

of the system. Temperatures of the system can be
consulted in the first screen of the network menu.

NOTE

When a circuit is in a high pressure setback, the
indication of capacity will be flashing. A high pressure
setback is a prevention of load-up or a forced load-
down caused by a too high pressure.

Summary of Contents for EWAP110MBYNN

Page 1: ...OPERATION MANUAL EWAP110MBYNN EWAP140MBYNN EWAP160MBYNN EWAP200MBYNN EWAP280MBYNN EWAP340MBYNN Packaged air cooled water chillers...

Page 2: ...first time make sure that it has been properly installed It is therefore necessary to carefully read the installation manual supplied with the unit and the recommendations listed in Checks before ini...

Page 3: ...8 1 18 16 11 3 4 17 13 14 15 2 9 5 6 21 19 12 7 22 9 10 10 21 EWAP200 340 EWAP110 160 EWAP110 160 EWAP200 340 1 Evaporator 12 Power supply intake 2 Condenser 13 Emergency stop S5E 3 Compressor M1C 14...

Page 4: ...flows through it This is done by turning the liquid refrigerant coming from the condenser into gaseous refrigerant Water in outlet connection The water inlet and outlet connection allow an easy connec...

Page 5: ...e circuit controller shuts down the circuit When the pressure returns to normal the safety device can be reset on the controller Pressure relief safety valve The safety valve is activated when the pre...

Page 6: ...on oil leakage If there is an oil leak call your local dealer 10 Stop valves Open the liquid line discharge and suction if provided stop valves completely 11 Air inlet outlet Check that the air inlet...

Page 7: ...e specifications For units in a DICN configuration the remote digital controllers of the units can be installed at a distance of up to 50 metres by using a 6 ray telephone cable with a maximum cable r...

Page 8: ...d capacity of that specific circuit When a circuit is OFF the following status information may appear one of the circuit safety devices is activated refer to Troubleshooting on page 15 the circuit is...

Page 9: ...controller is activated When a network safety occurs in a DICN configuration the slaves not detected by the network will function as stand alone units If a slave unit can not be found by the network t...

Page 10: ...reen of the network menu To consult information about the unit status To consult information about the pressures To consult actual operational information about the ambient temperature the total runni...

Page 11: ...he moment of the unit shutdown To check which were the evaporator and condenser inlet water temperature and the evaporator outlet water temperature To check which was the status of the compressors at...

Page 12: ...e capacity limitation 1 the capacity limitation is not active capacity limitation value of circuit 1 in case of capacity limitation 1 2 3 4 Defining the pump control settings The screen of the user se...

Page 13: ...in the service menu Refer to the installation manual used to define the free cooling mode free cooling is not active free cooling is based on ambient temperature free cooling is based on the differen...

Page 14: ...he waterflow through the evaporator stops after the flowstart timer has reached zero If the waterflow has not restarted during the countdown the unit will shut down PUMPLEAD refer to the pump control...

Page 15: ...hich contains the following information the time and date 2 Press h to consult the first screen This screen contains information about the unit name and the refrigerant used 3 Press h to consult the n...

Page 16: ...ty devices may be bridged or changed to a value other than the factory setting If the cause of the problem cannot be found call your local dealer Symptom 1 The unit does not start but the ON LED light...

Page 17: ...sed electrician RESET After pressure decrease push the button on the high pressure switch and reset the controller Symptom 5 4 Fan thermal protector is activated POSSIBLE CAUSES CORRECTIVE ACTION Mech...

Page 18: ...r local dealer Water supply Check if the water connection is still well fixed Check the water quality refer to the installation manual of the unit for specifications of the water quality Water filters...

Page 19: ...in group 1 all Wednesdays will work according to the settings in group 2 all Saturdays and Sundays will work according to the settings in group 3 all holiday days will work according to the settings...

Page 20: ...tween inlet water evaporator temperature and ambient temperature Floating setpoint Default value Lower limit Upper limit Maximum value C 3 0 0 0 5 0 D1 C 20 0 20 0 43 0 D2 a a rise in floating setpoin...

Page 21: ...0 ANNEX V SOFTWARE STRUCTURE g 0 1 2 q h q q g h h h g h g g h g h g h g h g h g h g h g g h g h g h g h g h h h h h g g g 2 f 4 4 4 4 2 4 4 4 4 4 4 4 0 4 4 g h g h g h 2 2 2 2 q h h g q 6 h g h g h g...

Page 22: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PW22677 1...

Reviews: