6
|
Application guidelines
Installer reference guide
50
ERGA04~08EAV3(A) + EHBH/X04+08EA/EJ6V+9W
Daikin Altherma 3 R W
4P629085-1 – 2020.08
Setup
▪
Connect power meter 1 to X5M/5 and X5M/6.
▪
Connect power meter 2 to X5M/3 and X5M/4.
"9.3.4 To connect the electricity meters"
Power meter types
▪
Power meter 1: Single- or three-phase power meter according to the power
supply of the outdoor unit.
▪
Power meter 2:
-
In case of a single-phase backup heater configuration, use a single-phase
power meter.
-
In other cases, use a three-phase power meter.
Example
Single-phase outdoor unit with a three-phase backup heater:
e
e
f
e
i
h
g
j
A
B
C
b
a
d
c
580
1 50
0
0
580
1 50
0
0
A
Outdoor unit
B
Indoor unit
C
DHW tank
a
Electrical cabinet (L
1
/N): Preferential kWh rate power supply
b
Electrical cabinet (L
1
/L
2
/L
3
/N): Normal kWh rate power supply
c
Power meter (L
1
/N)
d
Power meter (L
1
/L
2
/L
3
/N)
e
Fuse (L
1
/N)
f
Fuse (L
1
/L
2
/L
3
/N)
g
Outdoor unit (L
1
/N)
h
Indoor unit (L
1
/N)
i
Backup heater (L
1
/L
2
/L
3
/N)
j
Booster heater (L
1
/N)
6.6 Setting up the power consumption control
▪
The power consumption control:
-
Allows you to limit the power consumption of the entire system (sum of
outdoor unit, indoor unit, backup heater and optional booster heater).
-
Configuration: Set the power limitation level and how it has to be achieved via
the user interface.
▪
The power limitation level can be expressed as:
-
Maximum running current (in A)
-
Maximum power input (in kW)
▪
The power limitation level can be activated:
-
Permanently
-
By digital inputs