Breadcrumb Field code
Setting name
Range, step
Default value
Date
Value
Room
└─
Antifrost
1.4.1
[2-06]
R/W
0: Disabled
1: Enabled
1.4.2
[2-05]
R/W
4~16°C, step: 1°C
12°C
└─
Setpoint range
1.5.1
[3-07]
R/W
12~18°C, step: 1°C
12°C
1.5.2
[3-06]
R/W
18~30°C, step: 1°C
30°C
1.5.3
[3-09]
R/W
15~25°C, step: 1°C
15°C
1.5.4
[3-08]
R/W
25~35°C, step: 1°C
35°C
Room
1.6
[2-09]
R/W
-5~5°C, step: 0,5°C
0°C
1.7
[2-0A]
R/W
-5~5°C, step: 0,5°C
0°C
└─
Room comfort setpoint
1.9.1
[9-0A]
Heating comfort setpoint
R/W
[3-07]
~
[3-06]°C, step: 0,5°C
23°C
1.9.2
[9-0B]
Cooling comfort setpoint
R/W
[3-09]
~
[3-08]°C, step: 0,5°C
23°C
Main zone
2.4
0: Fixed
1: WD heating, fixed cooling
2: Weather dependent
└─
Heating WD curve
2.5
[1-00]
R/W
-40~5°C, step: 1°C
-10°C
2.5
[1-01]
R/W
10~25°C, step: 1°C
15°C
2.5
[1-02]
R/W
[9-01]~[9-00], step: 1°C
35°C
2.5
[1-03]
R/W
[9-01]~min(45, [9-00])°C , step: 1°C
25°C
└─
Cooling WD curve
2.6
[1-06]
R/W
10~25°C, step: 1°C
20°C
2.6
[1-07]
R/W
25~43°C, step: 1°C
35°C
2.6
[1-08]
R/W
[9-03]~[9-02]°C, step: 1°C
22°C
2.6
[1-09]
R/W
[9-03]~[9-02]°C, step: 1°C
18°C
Main zone
2.7
[2-0C]
R/W
0: Underfloor heating
1: Fancoil unit
2: Radiator
└─
Setpoint range
2.8.1
[9-01]
R/W
15~37°C, step: 1°C
25°C
2.8.2
[9-00]
R/W
[2-0C]=2:
37~65, step: 1°C
55°C
[2-0C]
≠
2:
37~55, step: 1°C
55°C
2.8.3
[9-03]
R/W
5~18°C, step: 1°C
5°C
2.8.4
[9-02]
R/W
18~22°C, step: 1°C
22°C
Main zone
2.9
[C-07]
R/W
0: LWT control
1: Ext RT control
2: RT control
2.A
[C-05]
R/W
0: -
1: 1 contact
2: 2 contacts
└─
Delta T
2.B.1
[1-0B]
R/W
3~10°C, step: 1°C
5°C
2.B.2
[1-0D]
R/W
3~10°C, step: 1°C
5°C
└─
Modulation
2.C.1
[8-05]
R/W
0: No
1: Yes
2.C.2
[8-06]
R/W
0~10°C, step: 1°C
5°C
└─
Shut off valve
2.D.1
[F-0B]
R/W
0: No
1: Yes
2.D.2
[F-0C]
R/W
0: No
1: Yes
Additional zone
3.4
0: Fixed
1: WD heating, fixed cooling
2: Weather dependent
└─
Heating WD curve
3.5
[0-00]
R/W
[9-05]~min(45,[9-06])°C, step: 1°C
35°C
3.5
[0-01]
R/W
[9-05]~[9-06]°C, step: 1°C
50°C
3.5
[0-02]
R/W
10~25°C, step: 1°C
15°C
3.5
[0-03]
R/W
-40~5°C, step: 1°C
-10°C
└─
Cooling WD curve
3.6
[0-04]
R/W
[9-07]~[9-08]°C, step: 1°C
8°C
Low ambient temp. for LWT add zone heating WD curve.
Leaving water value for high ambient temp. for LWT add zone cooling WD curve.
Low ambient temp. for LWT main zone cooling WD curve.
Cooling minimum
Room setpoint
Heating minimum
Heating maximum
Cooling minimum
Cooling maximum
Room sensor offset
Room sensor offset
Low ambient temp. for LWT main zone heating WD curve.
High ambient temp. for LWT main zone heating WD curve.
Setpoint mode
Leaving water value for high ambient temp. for LWT main zone heating WD curve.
Cooling maximum
Delta T cooling
Modulation
Max modulation
Setpoint mode
High ambient temp. for LWT main zone cooling WD curve.
Leaving water value for low ambient temp. for LWT main zone cooling WD curve.
Heating maximum
Thermostat type
High ambient temp. for LWT add zone heating WD curve.
Leaving water value for high ambient temp. for LWT add zone heating WD curve.
Installer setting at variance with
default value
Leaving water value for high ambient temp. for LWT main zone cooling WD curve.
Emitter type
Heating minimum
Leaving water value for low ambient temp. for LWT main zone heating WD curve.
Control
Field settings table
Activation
Delta T heating
Leaving water value for low ambient temp. for LWT add zone heating WD curve.
During cooling
During thermo