5/11
Breadcrumb Field code
Setting name
Range, step
Default value
Date
Value
Installer setting at variance with
default value
Field settings table
9.1
[0-00]
R/W
[9-05]~min(45,[9-06])°C, step: 1°C
35°C
9.1
[0-01]
R/W
[9-05]~[9-06]°C, step: 1°C
50°C
9.1
[0-02]
R/W
10~25°C, step: 1°C
15°C
9.1
[0-03]
R/W
-40~5°C, step: 1°C
-10°C
9.1
[0-04]
R/W
[9-07]~[9-08]°C, step: 1°C
8°C
9.1
[0-05]
R/W
[9-07]~[9-08]°C, step: 1°C
12°C
9.1
[0-06]
R/W
25~43°C, step: 1°C
35°C
9.1
[0-07]
R/W
10~25°C, step: 1°C
20°C
└─
Tank
9.1
[6-0D]
R/W
0: Reheat only
1: sched.
2: Scheduled only
9.1
[6-0A]
R/W
30~[6-0E]°C, step: 1°C
60°C
9.1
[6-0B]
R/W
30~min(50, [6-0E])°C, step: 1°C
45°C
9.1
[6-0C]
R/W
30~min(50, [6-0E])°C, step: 1°C
45°C
└─
Domestic hot water
9.2.1
[E-05]
[E-06]
[E-07]
R/W
0: No DHW (*4)
2: EKHW (*4)
3: Integrated (*5)
7: EKHWP (*4)
9.2.2
[D-02]
R/W
0: No
1: Secondary rtrn
2: Disinf. Shunt
9.2.4
[D-07]
R/W
0: No
1: Yes
└─
Back up heater
9.3.1
[E-03]
R/O
2: 3V (*1)
3: 6V (*2)
4: 9W (*3)
9.3.2
[5-0D]
R/W (*2)
R/O (*1)
(*3)
0: 230V, 1~ (*1) (*2)
1: 230V, 3~ (*2)
2: 400V, 3~ (*3)
9.3.3
[4-0A]
R/W
0: 1 (*1)
1: 1/1+2 (*2) (*3)
2: 1/2
3: 1/2 + 1/1+2 in emergency
9.3.4
[6-03]
R/W
0~10kW, step: 0,2kW
2
kW (*2)
3kW (*1)(*3)
9.3.5
[6-04]
R/O (*1)
R/W (*2)
(*3)
0~10kW, step: 0,2kW
0kW (*1)
4kW (*2)
6kW (*3)
9.3.6
[5-00]
R/W
0: Allowed
1: Not allowed
9.3.7
[5-01]
R/W
-15~35°C, step: 1°C
0°C
9.3.8
[4-00]
R/W
0: Disabled
1: Enabled
2: Only DHW
└─
Booster heater
9.4.1
[6-02]
R/W
0~10kW, step: 0,2kW
3kW (*4)
0kW (*5)
9.4.3
[8-03]
R/W
20~95 min, step: 5 min
50 min
9.4.4
[4-03]
R/W
0: Restricted
1: Allowed
2: Overlap
3: Compressor off
4: Legionella only
└─
Emergency
9.5.1
[4-06]
R/W
0: Manual
1: Automatic(normal SH/DHW ON)
2: Auto red SH/DHW ON
3: Auto red SH/DHW OFF
4: SH ON/DHW OFF
9.5.2
[7-06]
R/W
0: Disabled
1: Enabled
└─
Balancing
9.6.1
[5-02]
R/W
0: Disabled
1: Enabled
9.6.2
[5-03]
R/W
-15~35°C, step: 1°C
0°C
9.6.3
[5-04]
R/W
0~20°C, step: 1°C
10°C
9.6.4
[8-02]
R/W
0~10 hour, step: 0,5 hour
0,5 hour [E-07]=1
3 hour [E-07]
≠
1
9.6.5
[8-00]
R/W
0~20 min, step 1 min
1 min
9.6.6
[8-01]
R/W
5~95 min, step: 5 min
30 min
9.6.7
[8-04]
R/W
0~95 min, step: 5 min
95 min
Installer settings
9.7
[4-04]
0: Intermittent
1: Continuous
2: Off
└─
Benefit kWh power supply
Minimum running timer
Maximum running timer
Additional timer
Water pipe freeze prevention
Operation
Space heating priority
Priority temperature
Offset BSH setpoint
Anti-recycle timer
Emergency
Additional capacity step 2
Equilibrium
Equilibrium temperature
Operation
Capacity
BSH eco timer
Eco setpoint
Reheat setpoint
Domestic hot water
DHW pump
Solar
BUH type
Voltage
Configuration
Capacity step 1
Leaving water value for high ambient temp. for LWT add zone cooling WD curve.
Leaving water value for low ambient temp. for LWT add zone cooling WD curve.
High ambient temp. for LWT add zone cooling WD curve.
Low ambient temp. for LWT add zone cooling WD curve.
Heat up mode
Comfort setpoint
Leaving water value for high ambient temp. for LWT add zone heating WD curve.
Leaving water value for low ambient temp. for LWT add zone heating WD curve.
High ambient temp. for LWT add zone heating WD curve.
Low ambient temp. for LWT add zone heating WD curve.
HP Forced OFF
(*1) *3V_(*2) *6V_
(*3) *9W_(*4) EHB*_
(*5) EHV*_
(*6) *X*_(*7) *H*
(#) Setting is not applicable for this unit.
4P629091-1 - 2020.09