10
|
Configuration
Installer reference guide
159
ERGA04~08EAV3(A) + EHBH/X04+08EA/EJ6V+9W
Daikin Altherma 3 R W
4P629085-1 – 2020.08
3
Additional zone
Space heating/cooling
Main zone
Room
Tank
[3]
Additional zone
Setpoint screen
[3.1]
Schedule
[3.2]
Heating schedule
[3.3]
Cooling schedule
[3.4]
Setpoint mode
[3.5]
Heating WD curve
[3.6]
Cooling WD curve
[3.7]
Emitter type
[3.8]
Setpoint range
[3.9]
Control
[3.A]
Thermostat type
[3.B]
Delta T
[3.C]
WD curve type
Setpoint screen
Control the leaving water temperature for the additional zone via setpoint screen
[3]
Additional zone
.
See
133].
Schedule
Indicates if the desired leaving water temperature is according to a schedule.
See
148].
#
Code
Description
[3.1]
N/A
Schedule
:
▪
No
▪
Yes
Heating schedule
Define a heating temperature schedule for the additional zone via [3.2]
Heating
schedule
.
See
"10.3.7 Schedule screen: Example"
Cooling schedule
Define a cooling temperature schedule for the additional zone via [3.3]
Cooling
schedule
.
See
"10.3.7 Schedule screen: Example"
Setpoint mode
The setpoint mode of the additional zone can be independently set from the
setpoint mode of the main zone.
See