ERGA04~08EAV3(A) + EHBH/X04+08EA/EJ6V+9W
Daikin Altherma 3 R W
4P629085-1 – 2020.08
Setpoint range
For more information about
Setpoint range
#
Code
Description
Leaving water temperature range for the additional leaving water temperature
zone (= the leaving water temperature zone with the highest leaving water
temperature in heating operation and the lowest leaving water temperature in
cooling operation)
[3.8.1]
[9-05]
Heating minimum
: 15°C~37°C
[3.8.2]
[9-06]
Heating maximum
▪
[2‑0D]=2 (emitter type additional zone =
radiator)
37°C~65°C
▪
Else: 37°C~55°C
[3.8.3]
[9-07]
Cooling minimum
▪
5°C~18°C
[3.8.4]
[9-08]
Cooling maximum
▪
18°C~22°C
Control
The control type for the additional zone is read only. It is determined by the control
type of the main zone.
See
148].
#
Code
Description
[3.9]
N/A
Control
:
▪
Leaving water
if the control type of the
main zone is
Leaving water
.
▪
External room thermostat
if the control
type of the main zone is:
-
External room thermostat
,or
-
Room thermostat
.
Thermostat type
Only applicable in external room thermostat control.
#
Code
Description
[3.A]
[C‑06]
External room thermostat type for the additional
zone:
▪
1:
1 contact
. Connected to only 1 digital
input (X2M/35a)
▪
2:
2 contacts
. Connected to 2 digital inputs
(X2M/34a and X2M/35a)
Leaving water temperature: Delta T
For more information, see
148].