10
|
Configuration
Installer reference guide
148
ERGA04~08EAV3(A) + EHBH/X04+08EA/EJ6V+9W
Daikin Altherma 3 R W
4P629085-1 – 2020.08
#
Code
Description
[1.6]
[2-0A]
Room sensor offset
(user interface used as
room thermostat): Offset on the actual room
temperature measured by the user interface
used as room thermostat.
▪
–5°C~5°C, step 0.5°C
[1.7]
[2-09]
Room sensor offset
(external room sensor
option): Only applicable if the external room
sensor option is installed and configured.
▪
–5°C~5°C, step 0.5°C
Room comfort setpoint
Restriction:
Only applicable if:
▪
Smart Grid is enabled ([9.8.4]=
Smart grid
), and
▪
Room buffering is enabled ([9.8.7]=
Yes
)
If room buffering is enabled, the extra energy from photovoltaic panels is buffered
in the DHW tank and in the space heating circuit (i.e. heat up the room). With the
room comfort setpoints (cooling/heating) you can modify the maximum setpoints
that will be used when buffering the extra energy in the space heating circuit (i.e.
heat up the room).
#
Code
Description
[1.9.1]
[9-0A]
Heating comfort setpoint
▪
[3-07]~[3-06]°C
[1.9.2]
[9-0B]
Cooling comfort setpoint
▪
[3-09]~[3-08]°C
10.5.3 Main zone
Overview
The following items are listed in the submenu: