10
|
Configuration
Installer reference guide
175
ERGA04~08EAV3(A) + EHBH/X04+08EA/EJ6V+9W
Daikin Altherma 3 R W
4P629085-1 – 2020.08
INFORMATION
Risk of space heating capacity shortage for domestic hot water tank without internal
booster heater: In case of frequent domestic hot water operation, frequent and long
space heating/cooling interruption will happen when selecting the following:
Tank
>
Heat up mode
>
Reheat only
.
Disinfection
Applies only to installations with a domestic hot water tank.
The disinfection function disinfects the domestic hot water tank by periodically
heating the domestic hot water to a specific temperature.
CAUTION
The disinfection function settings MUST be configured by the installer according to
the applicable legislation.
#
Code
Description
[5.7.1]
[2‑01]
Activation
:
▪
0:
No
▪
1:
Yes
[5.7.2]
[2‑00]
Operation day
:
▪
0:
Every day
▪
1:
Monday
▪
2:
Tuesday
▪
3:
Wednesday
▪
4:
Thursday
▪
5:
Friday
▪
6:
Saturday
▪
7:
Sunday
[5.7.3]
[2‑02]
Start time
[5.7.4]
[2‑03]
Tank setpoint
:
55°C~75°C
[5.7.5]
[2‑04]
Duration
:
5~60 minutes
00.00
22.00
24.00
01.00
23.00
t
T
DHW
T
H
T
U
[2-02]
[2-03]
[2-04]
T
DHW
Domestic hot water temperature
T
U
User setpoint temperature
T
H
High setpoint temperature [2-03]
t
Time