3/11
Breadcrumb Field code
Setting name
Range, step
Default value
Date
Value
Installer setting at variance with
default value
Field settings table
3.6
[0-05]
R/W
[9-07]~[9-08]°C, step: 1°C
12°C
3.6
[0-06]
R/W
25~43°C, step: 1°C
35°C
3.6
[0-07]
R/W
10~25°C, step: 1°C
20°C
Additional zone
3.7
[2-0D]
R/W
0: Underfloor heating
1: Fancoil unit
2: Radiator
└─
Setpoint range
3.8.1
[9-05]
R/W
15~37°C, step: 1°C
25°C
3.8.2
[9-06]
R/W
[2-0D]=2:
37~65, step: 1°C
55°C
[2-0D]
≠
2:
37~55, step: 1°C
55°C
3.8.3
[9-07]
R/W
5~18°C, step: 1°C
5°C
3.8.4
[9-08]
R/W
18~22°C, step: 1°C
22°C
Additional zone
3.A
[C-06]
R/W
0: -
1: 1 contact
2: 2 contacts
└─
Delta T
3.B.1
[1-0C]
R/W
3~10°C, step: 1°C
5°C
3.B.2
[1-0E]
R/W
3~10°C, step: 1°C
5°C
Space heating / cooling
└─
Operation range
4.3.1
[4-02]
R/W
14~35°C, step: 1°C
2
2°C
4.3.2
[F-01]
R/W
10~35°C, step: 1°C
20°C
Space heating / cooling
4.4
[7-02]
R/W
0: 1 LWT zone
1: 2 LWT zones
4.5
[F-0D]
R/W
0: Continuous
1: Sample
2: Request
4.6
[E-02]
R/W (*6)
R/O (*7)
0: Reversible (*6)
1: Heating only (*7)
4.7
[9-0D]
R/W
0~8, step:1
0 : No limitation
1~4 : 50~80%
5~8 : 50~80% during sampling
6
Space heating / cooling
4.9
[F-00]
R/W
0: Restricted
1: Allowed
4.A
[D-03]
R/W
0: No
1: increase 2°C, span 4°C
2: increase 4°C, span 4°C
3: increase 2°C, span 8°C
4: increase 4°C, span 8°C
4.B
[9-04]
R/W
1~4°C, step: 1°C
1°C
4.C
[2-06]
R/W
0: Disabled
1: Enabled
Tank
5.2
[6-0A]
R/W
30~[6-0E]°C, step: 1°C
60°C
5.3
[6-0B]
R/W
30~min(50, [6-0E])°C, step: 1°C
45°C
5.4
[6-0C]
R/W
30~min(50, [6-0E])°C, step: 1°C
45°C
5.6
[6-0D]
R/W
0: Reheat only
1: sched.
2: Scheduled only
└─
Disinfection
5.7.1
[2-01]
R/W
0: No
1: Yes
5.7.2
[2-00]
R/W
0: Each day
1: Monday
2: Tuesday
3: Wednesday
4: Thursday
5: Friday
6: Saturday
7: Sunday
5.7.3
[2-02]
R/W
0~23 hour, step: 1 hour
1
5.7.4
[2-03]
R/W
[E-07]
≠
1 :
55~75°C, step: 5°C
70°C
[E-07]=1 : 60°C
60°C
5.7.5
[2-04]
R/W
[E-07]
≠
1: 5~60 min, step: 5 min
10 min
[E-07]=1: 40~60 min, step: 5 min
40 min
Tank
5.8
[6-0E]
R/W
(*4) : 40~75°C, step: 1°C
60°C
[E-07]=0
(*4) : 40~80°C, step: 1°C
80°C
[E-07]=5
(*5) : 40~60°C, step: 1°C
60°C
5.9
[6-00]
R/W
2~40°C, step: 1°C
25°C
Activation
Pump operation mode
Antifrost
Start time
Pump outside range
Maximum
Heat up mode
Reheat setpoint
Eco setpoint
High ambient temp. for LWT add zone cooling WD curve.
Unit type
Increase around 0°C
Leaving water value for low ambient temp. for LWT add zone cooling WD curve.
Heating minimum
Heating maximum
Delta T cooling
Overshoot
Cooling minimum
Cooling maximum
Space cooling OFF temp
Thermostat type
Emitter type
Low ambient temp. for LWT add zone cooling WD curve.
Hysteresis
Comfort setpoint
Delta T heating
Duration
Tank setpoint
Space heating OFF temp
Pump limitation
Number of zones
Operation day
(*1) *3V_(*2) *6V_
(*3) *9W_(*4) EHB*_
(*5) EHV*_
(*6) *X*_(*7) *H*
(#) Setting is not applicable for this unit.
4P629091-1 - 2020.09