9
|
Electrical installation
Installer reference guide
101
ERLA EHFZ03S18DJ3V
Daikin Altherma 3 R F
4P596821-1B – 2021.10
A
6
5
4
3
S3S S2S
B
A
B
X5M
3 4 5 6
3
Fix the cable with cable ties to the cable tie mountings.
9.3.6 To connect the domestic hot water pump
Wires: (2+GND)×0.75 mm²
DHW pump output. Maximum load: 2 A (inrush), 230 V AC, 1 A
(continuous)
[A.2.2]
Options
> [A.2.2.A]
DHW pump
[7.3]
Set schedules
> [7.3.7]
DHW pump
1
Open the following (see
"7.2.4 To open the indoor unit"
1
Top panel
1
2
3
2
Upper front panel
3
Upper switch box cover
2
Connect the domestic hot water pump cable to the appropriate terminals as
shown in the illustration below.