Absolute desired LWT
b
Weather-dependent desired LWT
#
Code
Description
N/A
[D-03]
▪
0 (disabled)
▪
1 (enabled) L=2°C,
R=4°C (−2°C<T
A
<2°C)
▪
2 (enabled) L=4°C,
R=4°C (−2°C<T
A
<2°C)
▪
3 (enabled) L=2°C,
R=8°C (−4°C<T
A
<4°C)
▪
4 (enabled) L=4°C,
R=8°C (−4°C<T
A
<4°C)
Leaving water temperature maximum modulation
ONLY applicable in room thermostat control and when modulation is enabled. The
maximum modulation (=variance) on the desired leaving water temperature
decided on the difference between the actual and desired room temperature, e.g.
3°C modulation means the desired leaving water temperature can be increased or
lowered by 3°C. Increasing the modulation results in better performance (less On/
OFF, faster heat up), but note that depending on the heat emitter, there MUST
ALWAYS be a balance (see the design and selection of the heat emitters) between
the desired leaving water temperature and the desired room temperature.
#
Code
Description
N/A
[8-06]
0°C~10°C
Weather-dependent cooling allowance
It is possible to disable weather-dependent cooling, meaning the desired leaving
water temperature in cooling operation does NOT depend on the outdoor ambient
temperature and this regardless whether weather-dependent is selected or NOT.
Both for the main leaving water temperature zone as for the additional leaving
water temperature zone, this can be set separately.
#
Code
Description
N/A
[1-04]
Weather-dependent cooling of the main leaving
water temperature zone is…
▪
0 (disabled)
▪
1 (enabled)
N/A
[1-05]
Weather-dependent cooling of the additional
leaving water temperature zone is…
▪
0 (disabled)
▪
1 (enabled)