10
|
Configuration
Installer reference guide
151
ERLA EHFZ03S18DJ3V
Daikin Altherma 3 R F
4P596821-1B – 2021.10
#
Code
Description
[A.6.3.1]
[4-08]
Mode
:
▪
0 (
No limitation
)(default): Disabled.
▪
1 (
Continuous
): Enabled: You can set one
power limitation value (in A or kW) to which
the system power consumption will be
limited for all the time.
▪
2 (
Digital inputs
): Enabled: You can set
up to four different power limitation values
(in A or kW) to which the system power
consumption will be limited when the
corresponding digital input asks.
[A.6.3.2]
[4-09]
Type
:
▪
0 (
Current
): The limitation values are set in
A.
▪
1 (
Power
)(default): The limitation values are
set in kW.
[A.6.3.3]
[5-05]
Amp. value
: Only applicable in case of full
time power limitation mode.
0 A~50 A, step 1 A
[A.6.3.4]
[5-09]
kW value
: Only applicable in case of full time
power limitation mode.
0 kW~20 kW, step 0.5 kW
Amp. limits for DI
: Only applicable in case of power limitation mode based
on digital inputs and based on current values.
N/A
[5-05]
Limit DI1
0 A~50 A, step 1 A
N/A
[5-06]
Limit DI2
0 A~50 A, step 1 A
N/A
[5-07]
Limit DI3
0 A~50 A, step 1 A
N/A
[5-08]
Limit DI4
0 A~50 A, step 1 A
kW limits for DI
: Only applicable in case of power limitation mode based on
digital inputs and based on power values.
N/A
[5-09]
Limit DI1
0 kW~20 kW, step 0.5 kW
N/A
[5-0A]
Limit DI2
0 kW~20 kW, step 0.5 kW
N/A
[5-0B]
Limit DI3
0 kW~20 kW, step 0.5 kW
N/A
[5-0C]
Limit DI4
0 kW~20 kW, step 0.5 kW