6
|
Application guidelines
Installer reference guide
47
ERLA EHFZ03S18DJ3V
Daikin Altherma 3 R F
4P596821-1B – 2021.10
6.7 Setting up an external temperature sensor
You can connect one external temperature sensor. It measures the indoor or
outdoor ambient temperature. We recommend to use an external temperature
sensor in the following cases:
Indoor ambient temperature
▪
In room thermostat control, the user interface is used as room thermostat and it
measures the indoor ambient temperature. Therefore, the user interface must
be installed on a location:
-
Where the average temperature in the room can be detected
-
That is NOT exposed to direct sunlight
-
That is NOT near a heat source
-
That is NOT affected by outside air or air draught because of, for example, door
opening/closing
▪
If this is NOT possible, we recommend to connect a remote indoor sensor (option
KRCS01-1).
▪
Setup: For installation instructions, see the installation manual of the remote
indoor sensor.
▪
Configuration: Select room sensor [A.2.2.B].
Outdoor ambient temperature
▪
In the outdoor unit, the outdoor ambient temperature is measured. Therefore,
the outdoor unit must be installed on a location:
-
At the north side of the house or at the side of the house where the most heat
emitters are located
-
That is NOT exposed to direct sunlight
▪
If this is NOT possible, we recommend to connect a remote outdoor sensor
(option EKRSCA1).
▪
Setup: For installation instructions, see the installation manual of the remote
outdoor sensor.
▪
Configuration: Select outdoor sensor [A.2.2.B].
▪
When the power saving functionality of the outdoor unit is active (see
110]), the outdoor unit is turned down to reduce standby
energy losses. As a result, the outdoor ambient temperature is NOT read out.
▪
If the desired leaving water temperature is weather dependent, the full time
outdoor temperature measurement is important. This is another reason to install
the optional outdoor ambient temperature sensor.
INFORMATION
The external outdoor ambient sensor data (either averaged or instantaneous) is used
in the weather-dependent control curves and in the automatic heating/cooling
changeover logic. To protect the outdoor unit, the internal sensor of the outdoor unit
is always used.