OPERATION MODE SETTINGS

8. 

Any one of the following operation modes can be selected for the 
fi lter auto cleaning of the self-clean panel.

Operation mode

Description

(1)  Scheduled 

timer operation

Performs fi lter auto cleaning during the 
designated period selected from eight 
periods.

(2)  00:00-to-03:00 

operation

Performs fi lter auto cleaning during the 
factory-set period of time (00:00 to 03:00).

(3)  Auto control 

operation

Performs fi lter auto cleaning according to the 
control reference.

In consultation with the customer, set the desired operation mode 
by referring to the instructions on 

 Filter Auto cleaning 

 and 

 Filter 

Auto clean setting 

 in the operation manual for the Self Cleaning 

decoration panel.
At the time of delivery, refer to the contents of descriptions (1) 
through (3) in the above table and explain the customer when fi lter 
auto cleaning will start.

FIELD SETTINGS

9. 

Make settings in consultation with the customer according to the 
installation and usage conditions of the air conditioner. The 
following three settings are possible.

Dust quantity settings.

9-1 

Make settings according to the quantity of dust in the room.

Standard quantity of dust (General offi ces)

• 

Large quantity of dust (Stores dealing in clothing)

• 

Panel indicator (green) On/Off.

9-2 

The panel indicator (green) can display the following operating 
conditions. Make indicator settings according to the request of the 
customer.

Indicator

Operating conditions

Remarks

Green

Lit

Air-conditioning 

operation

The indicator is turned off 

before shipping.

Flash-

ing

Filter auto cleaning

The red lamp to inform the customer of the time of dust collection 
will not be turned off.

Make fi eld settings according to the installation manual of the 
remote controller. (Settings in bold cells are made before shipping.)

Setting 

item

Mode

No.

FIRST
CODE

NO.

SECOND CODE NO.

01

02

03

04

Dust 
quantity 
settings

14 

(24)

(9)

Standard 
quantity of 
dust

Large 
quantity of 
dust

Panel 
indicator 
(green) 
on/off

14 

(24)

(4)

On while in 
air-conditioning 
operation and 
fi lter cleaning 
operation.

Possible to 
turn on while 
in fi lter 
cleaning 
operation only.

Off while in 
air-conditioning 
operation and fi lter 
cleaning operation.

 *  Factory  settings

TEST OPERATION

10. 

Perform the test operation of the Self Cleaning decoration panel 
after the test operation of the indoor unit is fi nished.
The test operation of the Self Cleaning decoration panel is not 
possible while the indoor unit is in operation.

Note

Perform the test operation of the product after referring to “a. Test 
items on completion of work”.

Check that the EL. COMPO. BOX lids of the 

10-1 

indoor unit, outdoor unit, and self-clean 
panel, respectively, are closed.

Turn the indoor unit power on.

10-2 

The panel will go into initialization operation after the power is 
turned on.

Conduct the test operation of the panel two 

10-3 

minutes after the power is turned on.

Confi rm the cleaning operation of the fi lter with the remote 
controller.

Test operation method with remote controller

Stop the operation of the panel if the panel is in air-conditioning 

1. 

operation.
Continue pressing the Cancel button at least 4 seconds while the 

2. 

backlight is lit. The local setting menu will appear.
Select 

3. 

 Filter auto clean test 

 from the local setting menu, and 

press the Menu/Enter button.
“ 

4. 

 ” will appear on the basic screen. 

The display will disappear when the test operation is fi nished.
The required test operation time is approximately 10 minutes (in 
the case of setting the standard quantity of dust).

1.
2.

Set temperature

28

°C

Cool

Return

Setting

Press and hold 
Cancel button for 
4 seconds or 
longer during 
backlight lit.

3.

Return

Setting

Field setting
Outdoor status display
Fan forced operation ON
Main/Sub changeover
Filter element sign OFF

Filter auto clean test

Brush/Filter Sign OFF

1/2

Press Menu/Enter 
button.

4.

Set temperature

28

°C

Cool

Return

Setting

“Filter auto cleaning” 
will be displayed.

Backlight for LCD

Press any button and the backlight will be lit for approximately 
30 seconds.
Perform the operation of buttons while the backlight is lit (except the 
On/Off button).

Test items on test operation

Test items

Remedy

Check 

result

Is the fi lter rotating?

Check the 
connector 
connections.

Are the fl aps fi xed horizontally?

Is “  

 ” displayed on the screen of 

the remote controller?

The remote controller will display “AH” if the self-clean panel has 

an error.

Note

After the test operation of the product is fi nished, refer to “b. Test 
items before delivery” in the installation manual.

01_EN_3P257556-1.indd   10

01_EN_3P257556-1.indd   10

9/3/2009   4:05:41 PM

9/3/2009   4:05:41 PM

Summary of Contents for BYCQ140CGW1

Page 1: ...er Auto Cleaning Function Self Cleaning decoration panel INSTALLATION MANUAL English Installation manual Self Cleaning decoration panel BYCQ140CGW1 00_CV_3P257556 1 indd 1 00_CV_3P257556 1 indd 1 9 2...

Page 2: ...evention of TV and radio interference Depending on the incoming signal strength a distance of 1 meter may not be sufficient to eliminate noise Pay the utmost attention to the transportation of the pro...

Page 3: ...er the connecting pipe and attachment and ask the customer to keep them Point of operation explanation In addition to the general usage of the air conditioner it is necessary to explain the descriptio...

Page 4: ...the backside of the protective corrugated cardboard Protective corrugated cardboard top The accessories are on the backside Protective corrugated cardboard bottom Note Do not impose force on the swin...

Page 5: ...ovided with the indoor unit Attaching spacer accessory 1 5 1 Indoor unit Remove the bypass hole closure material and peel off the 1 seal and holding tape 3 2 Seal 3 Holding tape Indoor unit 1 Screws 2...

Page 6: ...IONS FOR INDOOR UNIT Furthermore pull out the lead wires disconnected from the corner decoration cover with the display in 4 PREPARA TIONS FOR PANEL from the corner hole carefully so that the lead wir...

Page 7: ...redundant portions of the clamps from their roots after the both ends are secured Tighten the clamps Cut the roots Clamp accessory 5 Return the connected lead wires to the space between the 4 indoor...

Page 8: ...l at the request of the customer Attaching suction grille 7 1 Select either the hook A or B and hook the claws of the suction grille Note The suction grille may be damaged if the wrong hooking side is...

Page 9: ...rds while the suction grill is closed Check that the fall prevention cords do not protrude from the suction grille before closing the suction grille Suction grille Must not protrude Fall prevention co...

Page 10: ...m the suction grille before closing the suction grille Suction grille Must not protrude Fall prevention cord Attaching decoration corner covers 7 4 Connect the decoration corner cover with the display...

Page 11: ...tings TEST OPERATION 10 Perform the test operation of the Self Cleaning decoration panel after the test operation of the indoor unit is finished The test operation of the Self Cleaning decoration pane...

Page 12: ...3P257556 1 EM09A038 0909 HT 00_CV_3P257556 1 indd 2 00_CV_3P257556 1 indd 2 9 2 2009 9 03 28 AM 9 2 2009 9 03 28 AM...

Reviews: