Capacity tables
3 - 1
Cooling/Heating capacity tables
1
3
COOLING
Model
Tamb (°C)
20
25
30
35
40
43
LWE (°C)
CC
PI
CC
PI
CC
PI
CC
PI
CC
PI
CC
PI
00
6
7
6.01
1.56
5.73
1.75
5.43
1.95
5.12
2.16
4.80
2.39
4.59
2.53
11
6.81
1.57
6.50
1.77
6.17
1.98
5.83
2.21
5.30
2.32
4.98
2.38
13
7.23
1.57
6.90
1.78
6.56
2.00
6.20
2.23
5.56
2.28
5.18
2.30
16
7.88
1.56
7.54
1.78
7.17
2.01
6.79
2.26
5.95
2.22
5.46
2.18
20
8.80
1.55
8.42
1.79
8.03
2.03
7.63
2.29
6.48
2.13
5.82
1.99
00
7
7
7.15
2.05
6.84
2.28
6.50
2.52
6.13
2.77
5.35
2.68
4.89
2.59
11
8.09
2.09
7.73
2.34
7.34
2.59
6.94
2.87
5.84
2.62
5.21
2.43
13
8.57
2.11
8.20
2.36
7.79
2.63
7.36
2.91
6.09
2.59
5.36
2.34
16
9.33
2.13
8.92
2.40
8.49
2.68
8.03
2.97
6.46
2.53
5.57
2.20
20
10.4
2.16
9.9
2.44
9.48
2.73
8.99
3.04
6.96
2.44
5.82
1.99
00
8
7
8.24
2.43
7.90
2.68
7.52
2.94
7.10
3.23
5.68
2.86
4.87
2.59
11
9.26
2.49
8.87
2.76
8.45
3.05
7.79
3.31
6.12
2.80
5.18
2.43
13
9.79
2.52
9.38
2.80
8.93
3.10
8.14
3.36
6.34
2.77
5.33
2.35
16
10.6
2.57
10.17
2.86
9.69
3.17
8.68
3.41
6.67
2.71
5.55
2.20
20
11.7
2.63
11.3
2.94
10.75
3.26
9.39
3.48
7.09
2.61
5.80
1.99
HEATING (Peak values)
Model
LWC
30
35
40
45
50
Tamb
HC
PI
HC
PI
HC
PI
HC
PI
HC
PI
00
6
-15
3.93
1.48
3.67
1.59
3.47
1.71
3.33
1.84
3.25
1.99
-10
4.65
1.52
4.32
1.65
4.07
1.79
3.89
1.94
3.78
2.10
-7
5.14
1.54
4.77
1.68
4.49
1.83
4.28
1.99
4.15
2.16
-2
6.06
1.57
5.62
1.72
5.28
1.88
5.03
2.06
4.87
2.25
2
6.89
1.57
6.38
1.74
6.00
1.91
5.72
2.11
5.53
2.31
7
8.03
1.57
7.45
1.75
7.00
1.94
6.68
2.15
6.47
2.37
00
7
-15
4.87
1.82
4.62
1.94
4.43
2.08
4.30
2.23
4.24
2.40
-10
5.67
1.88
5.34
2.02
5.09
2.18
4.92
2.36
4.82
2.55
-7
6.21
1.91
5.83
2.07
5.55
2.24
5.35
2.42
5.23
2.63
-2
7.23
1.95
6.77
2.13
6.42
2.32
6.17
2.52
6.02
2.75
2
8.14
1.97
7.61
2.16
7.21
2.37
6.92
2.59
6.74
2.83
7
9.40
1.98
8.79
2.19
8.32
2.42
7.98
2.66
7.78
2.92
00
8
-15
5.42
2.06
5.16
2.19
4.97
2.34
4.86
2.51
4.80
2.70
-10
6.27
2.13
5.93
2.29
5.68
2.46
5.51
2.65
5.42
2.86
-7
6.84
2.17
6.46
2.34
6.17
2.53
5.97
2.73
5.86
2.95
-2
7.92
2.22
7.45
2.41
7.10
2.62
6.85
2.85
6.70
3.10
2
8.9
2.26
8.35
2.46
7.93
2.69
7.65
2.93
7.47
3.20
7
10.2
2.28
9.58
2.51
9.10
2.76
8.76
3.02
8.56
3.31
HEATING (integrated values*)
Model
LWC
30
35
40
45
50
Tamb
HC
PI
HC
PI
HC
PI
HC
PI
HC
PI
00
6
-15
3.50
1.40
3.27
1.51
3.09
1.62
2.97
1.75
2.89
1.89
-10
4.14
1.45
3.85
1.56
3.62
1.70
3.46
1.84
3.36
2.00
-7
4.52
1.45
4.20
1.58
3.95
1.72
3.77
1.87
3.65
2.03
-2
5.27
1.46
4.89
1.60
4.59
1.75
4.38
1.92
4.24
2.10
2
5.92
1.45
5.49
1.60
5.16
1.76
4.92
1.94
4.76
2.13
7
8.03
1.57
7.45
1.75
7.00
1.94
6.68
2.15
6.47
2.37
00
7
-15
4.34
1.73
4.11
1.85
3.94
1.98
3.83
2.12
3.77
2.28
-10
5.04
1.79
4.75
1.92
4.53
2.07
4.38
2.24
4.29
2.42
-7
5.46
1.80
5.13
1.94
4.88
2.10
4.71
2.28
4.60
2.47
-2
6.29
1.81
5.89
1.98
5.59
2.15
5.37
2.35
5.23
2.56
2
7.00
1.81
6.55
1.99
6.20
2.18
5.96
2.38
5.80
2.61
7
9.40
1.98
8.79
2.19
8.32
2.42
7.98
2.66
7.78
2.92
00
8
-15
4.82
1.96
4.59
2.08
4.43
2.23
4.32
2.39
4.27
2.56
-10
5.58
2.03
5.28
2.17
5.06
2.34
4.91
2.52
4.82
2.72
-7
6.02
2.04
5.69
2.20
5.43
2.37
5.26
2.57
5.15
2.78
-2
6.89
2.07
6.48
2.25
6.17
2.44
5.96
2.65
5.83
2.88
2
7.6
2.08
7.18
2.27
6.82
2.47
6.58
2.70
6.43
2.94
7
10.2
2.28
9.58
2.51
9.10
2.76
8.76
3.02
8.56
3.31
* The integrated heating capacity and power
input, is the average heating capacity and
power input during 1 cycle. (from end of
defrost till end of the next defrost).
SYMBOLS
CC
: Cooling capacity at maximum operating frequency, measured acc.
Eurovent 6/C/003-2006 (kW)
HC
: Heating capacity at maximum operating frequency, measured acc.
Eurovent 6/C/003-2006 (kW)
PI
: Power input (kW)
LWE
: Leaving Water Evaporator temperature (°C)
LWC
: Leaving Water Condensor temperature (°C)
Tamb
: Ambient temperature (°C) RH=85%
NOTES
1
Cooling capacity
Capacity is according to Eurovent rating standard 6/C/003-2006 and valid for
chilled water range Dt = 3
∼
8°C
2
Heating capacity
Capacity is according to Eurovent rating standard 6/C/003-2006 and valid for
chilled water range Dt = 3
∼
8°C
3
Power input
Power input is total of indoor and outdoor unit, except the circulation pump;
according to Eurovent rating standard 6/C/003-2006.
Pump power input to be added = 60 W (according EN14511).
For the optional model with heatertape (V38) when ambient temperature
becomes lower than 4°C: add power input of 60W
3TW57782-1A
Summary of Contents for Altherma EDLQ011-016AA6V3
Page 1: ...technical data EEDEN09 720 Altherma TM ...
Page 3: ...technical data EEDEN09 720 Altherma TM ...
Page 4: ... AlthermaTM AlthermaTM 4 A l t h e r A l t h e r R 4 1 0 A Heating only Heat pump ...
Page 6: ......
Page 7: ...technical data Part 1 4 ERHQ006 008AD EKHBH X008AA EEDEN09 720 Altherma TM ...
Page 8: ......
Page 20: ......
Page 35: ...technical data Part 2 4 ERHQ011 016AA ERHQ011 016AAW1 EKHBH X 016AB EEDEN09 720 Altherma TM ...
Page 36: ......
Page 52: ......
Page 68: ......
Page 84: ......
Page 176: ......
Page 196: ......
Page 216: ......
Page 236: ......
Page 237: ...technical data Part 4 4 EKHWS B EKHWE EKSOLHWAV1 EKRTW EKRTR EEDEN09 720 Altherma TM ...
Page 238: ......
Page 264: ......
Page 270: ......