• Altherma
TM
• Monobloc
87
• Monobloc • EDHQ011-016AA6V3
2
Specifications
3
2
2-1 NOMINAL CAPACITY AND NOMINAL INPUT
EDHQ011AA6V3
EDHQ014AA6V3
EDHQ016AA6V3
Condition 1
Heating capacity
Nominal
kW
11.20
14.00
16.00
Heating PI
Nominal
kW
2.47
3.20
3.79
COP
Nominal
4.54
4.37
4.22
Condition 2
Heating capacity
Nominal
kW
10.87
13.10
15.06
Heating PI
Nominal
kW
3.22
3.91
4.62
COP
Nominal
3.37
3.35
3.26
Notes
Condition 1: cooling Ta 35°C - LWE 18°C (Dt=5°C); heating Ta DB/WB 7°C/6°C - LWC 35°C (Dt=5°C)
Condition 2: cooling Ta 35°C - LWE 7°C (Dt=5°C); heating Ta DB/WB 7°C/6°C - LWC 45°C (Dt=5°C)
2-2 TECHNICAL SPECIFICATIONS
EDHQ011AA6V3
EDHQ014AA6V3
EDHQ016AA6V3
Casing
Colour
Ivory white
Material
Painted galvanised steel
Dimensions
Unit
Height
mm
1,418
Width
mm
1,435
Depth
mm
382
382
382
Packing
Height
mm
1,557
Width
mm
1,500
Depth
mm
430
430
430
Weight
Unit
kg
180
180
180
Packed unit
kg
200
200
200
Packing
Material
Wood
Carton
Plastic foil
Weight
kg
20
20
20
Operation Range
Heating - Ambient
Min
°CDB
-15
-15
-15
Max
°CDB
35
35
35
Heating - Waterside Min
°C
15
15
15
Max
°C
55
55
55
Domestic hot water
-Ambient
Min
°CDB
-15
-15
-15
Max
°CDB
43
43
43
Domestic hot water
- Waterside
Min
°C
25
25
25
Max
°C
80
80
80
Sound Level
(nominal)
Heating
Sound
Power
dBA
64
64
66
Sound
Pressure
dBA
51
51
52
Sound Level (Night
quiet)
Heating
Sound
Pressure
dBA
42
42
43
Refrigerant
Type
R-410A
Charge
kg
2.95
2.95
2.95
Control
Electronic expansion valve
Nr of Circuits
1
1
1
Refrigerant Oil
Type
Daphne FVC68D
Charged Volume
l
1.0
1.0
1.0
Defrost Method
Pressure equalising
Defrost Control
Sensor for outdoor heat exchanger temperature
Capacity Control Method
Inverter controlled
Safety Devices
High pressure switch
Fan motor thermal protector
Fuse
Notes
The sound pressure level is measured via a microphone at a certain distance from the unit. It is a
relative value depending on the distance and acoustic environment. Refer to sound spectrum drawing
for more information.
Conditions: Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C)
Conditions: Ta 35°C - LWE 7°C (DT = 5°C)
15°-25°C: BUH only, no heat pump operation = during commisioning
including PHE + back-up heater / excluding expansion vessel
E(D)(B)L* model can reach -20°C / E(D)(B)L*6W1 model can reach -25°C but without capacity
guarantee
Summary of Contents for Altherma EDLQ011-016AA6V3
Page 1: ...technical data EEDEN09 720 Altherma TM ...
Page 3: ...technical data EEDEN09 720 Altherma TM ...
Page 4: ... AlthermaTM AlthermaTM 4 A l t h e r A l t h e r R 4 1 0 A Heating only Heat pump ...
Page 6: ......
Page 7: ...technical data Part 1 4 ERHQ006 008AD EKHBH X008AA EEDEN09 720 Altherma TM ...
Page 8: ......
Page 20: ......
Page 35: ...technical data Part 2 4 ERHQ011 016AA ERHQ011 016AAW1 EKHBH X 016AB EEDEN09 720 Altherma TM ...