Installation
7 - 1
Drainage instructions
2
7
EKHBDP
1. Refer to psychometric chart for more information.
2. If condensation is expected, installation of EKHBDP - drainpan kit must be considered.
Le
aving
wate
r tem
p
e
ratu
re
[°C]
Dry bulb temperature [°C]
Example:
With ambient temperature of 25°C and
relative humidity of 40%.
If leaving water temperature is below
12°C, condensation on water piping
will happen.
Maximum leaving water
temperature cooling mode
= 22°C
Relative humidity 40%
Relative humidity 60%
Relative humidity 80%
Le
avin
g
w
a
te
r te
mp
er
at
u
re [
°C]
4TW57759-3
Leaving water temperature limit to prevent condesation
Summary of Contents for Altherma EDLQ011-016AA6V3
Page 1: ...technical data EEDEN09 720 Altherma TM ...
Page 3: ...technical data EEDEN09 720 Altherma TM ...
Page 4: ... AlthermaTM AlthermaTM 4 A l t h e r A l t h e r R 4 1 0 A Heating only Heat pump ...
Page 6: ......
Page 7: ...technical data Part 1 4 ERHQ006 008AD EKHBH X008AA EEDEN09 720 Altherma TM ...
Page 8: ......
Page 20: ......
Page 35: ...technical data Part 2 4 ERHQ011 016AA ERHQ011 016AAW1 EKHBH X 016AB EEDEN09 720 Altherma TM ...
Page 36: ......
Page 52: ......
Page 68: ......
Page 84: ......
Page 176: ......
Page 196: ......
Page 216: ......
Page 236: ......
Page 237: ...technical data Part 4 4 EKHWS B EKHWE EKSOLHWAV1 EKRTW EKRTR EEDEN09 720 Altherma TM ...
Page 238: ......
Page 264: ......
Page 270: ......