![DAB MCE-30/P Instruction For Installation And Maintenance Download Page 82](http://html1.mh-extra.com/html/dab/mce-30-p/mce-30-p_instruction-for-installation-and-maintenance_495449082.webp)
ENGLISH
78
4.2.2.1 Flow
sensors
The flow sensor must be inserted on the delivery manifold on which all pumps are connected, and the
electrical connection can be made on any of the inverters.
The flow sensors can be connected in two ways:
one sensor only
the same number of sensors as inverters
The setting is entered on parameter FI. Multiple sensors are useful when a specific flow rate is required on
each pump, and enhance protection against dry running operation. To use multiple flow sensors, parameter
Fl must be set to multiple sensors and each flow sensor must be connected to the inverter that controls the
pump delivery where the sensor is located.
4.2.2.2 Pressure
sensors
The pressure sensor must be inserted on the delivery manifold. There can be more than one pressure
sensor, and in this case the pressure reading will be the average value of all those present. To use multiple
pressure sensors, the connectors are simply inserted in the relative inputs and no parameter needs to be
set. The number of pressure sensors installed can vary as required between one and the maximum number
of inverters present.
4.2.3
Connection and setting of the optical coupling inputs
The optical coupling inputs, see par. 2.2.4 and 6.6.13, are used to activate the float, auxiliary pressure,
system disabling and low suction pressure functions. The functions are indicated respectively by the
messages F1, Paux, F3, F4. If activated, the Paux function boosts the pressure in the system to the set
pressure, see par. 6.6.13.3. The functions F1, F3, F4 stop the pump for 3 different reasons, see par.
6.6.13.2, 6.6.13.4, 6.6.13.5.
When using a multi-inverter system, the optical coupling inputs must be used with the following precautions:
the contacts that perform the auxiliary pressures must be connected in parallel on all the inverters so
that the same signal arrives on all the inverters.
the contacts that perform the functions F1, F3, F4 may be connected either with independent
contacts for each inverter, or with only one contact connected in parallel on all the inverters (the
function is activated only on the inverter at which the command arrives).
The parameters for setting the inputs I1, I2, I3, I4 are part of the sensitive parameters, so setting one of
these on any inverter means that they are automatically aligned on all the inverters. As the setting of the
inputs not only selects the function, but also the type of polarity of the contact, the function associated with
the same type of contact will perforce be found on all the inverters. For the above reason, when using
independent contacts for each inverter (as is possible for the functions F1, F3, F4), these must all have the
same logic for the various inputs with the same name; that is, for the same input, either normally open
contacts are used for all the inverters or normally closed ones.
Summary of Contents for MCE-30/P
Page 278: ...274 1 276 2 279 3 280 4 282 5 283 6 4 20 284 7 285 8 286 9 287 10 290 11 290 12 292...
Page 279: ...275 IEC 60634...
Page 280: ...276 1 6 MCE 55 P e MCE 30 P 1 1 1...
Page 282: ...278 2 5 2 1 2 1 2 2 1 1 2 1 2 L L L 2 2 4 15...
Page 283: ...279 2 2 2 1 2 2 1 1 4 3 1 RST 2 2 4 3 1 8 3 3...
Page 284: ...280 AS 3 3 2 2 1 2 4 3 1 UVW 4 2 4 3 50 60 200 1...
Page 286: ...282 4 2 2 3 Press e Flow 5 A B C D d1 d2...
Page 291: ...287 3 9 64 X 128 4 MODE SET 10 7 MODE 1 SET 7 3 EEprom SET 6 SET MODE...
Page 292: ...288 3 1 9 3 2 1 2 3 2 1 MODE SET MODE 8 2 2 5 5 5 2 2 8...
Page 294: ...290 3 2 2 11 SET 10 15 12 11...
Page 296: ...292 12 11 13 GO SB...
Page 297: ...293 4 4 1 Link 8 4 2 4 2 1 Link 2 Link 5...
Page 300: ...296 4 3 1 2 1 4 3 1 3 SET MODE LA RC FN MS FS FL AC AE O1 1 O2 2 4 4 ET 6 6 9 FL...
Page 326: ...322 BL 10 6 24 24 30 LP 295 348 HP OT TE 100 C 85 C OB BT 120 C 100 C OC 10 6 OF 10 6 29...
Page 327: ...323 8 8 1 PMW 4 2 8 2 8 3 8 3 SET EE EEprom FLASH...
Page 494: ...490 1 492 2 495 3 496 4 498 5 499 6 4 20 mA 500 7 501 8 502 9 503 10 506 11 506 12 508 13 523...
Page 495: ...491 IEC 364 inverter...
Page 496: ...492 1 Inverter inverter inverter 6 inverter MCE 55 P MCE 30 P 1 1 1...
Page 502: ...498 4 2 2 3 Press Flow 5 A B C D d1 d2...
Page 507: ...503 3 9 oled 64 X 128 4 MODE SET 9 inverter 7 MODE 1 SET 7 3 EEprom SET 6 SET MODE...
Page 508: ...504 3 1 9 3 2 1 2 3 2 1 MODE SET Setpoint MODE 8 ONOMA TOY MENOY 2 Setpoint 2 5 5 5 2 2 8...
Page 512: ...508 12 11 12 GO SB FAULT...
Page 543: ...539 8 8 1 PMW 4 2 8 2 inverter 8 3 8 3 inverter SET EEPROM FLASH setpoint...
Page 599: ...595...