continued from the previous page
Number of Pages
Parameter
Description
Field
Unit of
measure
DAB
Standard
SetUp
18. Cnt.Strt.P2P3P4
Choice of the minimum time within which the
second start, after the first, is NOT allowed for
the SUPPLY pump P2, P3, P4 or the BACKUP
pump.
Any intervention keeps the pump blocked until
the end of the set time.
In this interval of time the pump start delay is
indicated with the message WAIT.
0-:-600 sec.
10
19. Danger Pres.
Pressure value for which the control unit goes
into alarm status for overpressure.
The control unit blocks the system if the
pressure remains above the set value for more
than 5 seconds.
As soon as the pressure returns to normal, the
system is enabled (only after 5 seconds).
The protection is indicated in remote mode.
0,00-:-30 bar
10,00
20. Min.Pres.Al.H2O
Pressure set point to be set based on the
pressure in the delivery circuit.
The system is stopped if the pressure falls
below the set point for more than 1 minute: the
display shows
AL H2O
.
Attempted automatic reset 3 times after one
minute and total block with manual reset at the
fourth intervention. At this point the control
unit indicates AL 64: water lack.
0,00-:-25,5 bar
0,5
26. Pump Mnt.Interv.
Setting of the pump maintenance hours.
Mnt.Interv. P1, Mnt.Interv. P2, Mnt.Interv.P3,
Mnt.Interv. P4
0-:-99999 hours
4500
27. Op. Hours P1
Hours worked by pump P1
0-:-99999 hours
28. Op. Hours P2
Hours worked by pump P2
0-:-99999 hours
29. Op. Hours P3
Hours worked by pump P3
0-:-99999 hours
30. Op. Hours P4
Hours worked by pump P4
0-:-99999 hours