68
•
DM-NVX-35x(C) Encoders/Decoders
Product Manual – DOC. 7839M
On the LEX device, the <UsbRemoteDeviceId_F> and
<UsbRemoteDeviceId2_F> through <UsbRemoteDeviceId7_F> serial
output joins report the MAC address of each REX device to which the
LEX device is to be paired.
•
For Layer 3 transport:
a.
Copy the IP address (UsbLocalDeviceIpAddress) of the LEX device into
the <UsbRemoteDeviceIpAddress> serial input join on the REX device.
On the REX device, the <UsbRemoteDeviceIpAddress_F> serial output join
reports the IP address of the LEX device to which the REX device is to be
paired.
b.
Copy the IP address (UsbLocalDeviceIpAddress) of the REX device into
the <UsbRemoteDeviceIpAddress> serial input join on the LEX device.
On the LEX device, the <UsbRemoteDeviceIpAddress_F> serial output join
reports the IP address of the REX device to which the LEX device is to be
paired.
5.
Do either of the following:
•
Trigger the <Pair> digital input join on all DM NVX devices (LEX and REX).
•
Trigger the <AutomaticUSBPairingEnabled> digital input join on all DM NVX
devices (LEX and REX).
To remove pairing between DM NVX devices, do either of the following:
•
If automatic USB pairing is not enabled, trigger the <RemovePairing> digital
input join on each DM NVX device.
•
If automatic USB pairing is enabled, do either of the following:
-
For Layer 2, enter
00:00:00:00:00:00
or an empty string into the
<UsbRemoteDeviceId> serial input join.
-
For Layer 3, enter an unused IP address into the
<UsbRemoteDeviceIpAddress> serial input join.
For additional information about configuration of USB routing, refer to the SIMPL
Windows help file.