Appendix
External Interfaces
1TC Input #4 Jumper Positions
Analog Input
Jumper
Number
Placement
(4-20mA)
Placement
(0-10V)
Input #4 J1-9
& J1-10
JMP10
OUT
OUT
JMP11
OUT
IN
JMP13
IN
IN
JMP22
IN
OUT
NOTE: Signal is not ground-isolated. Customer’s interface must be isolated from ground (or ground loop damage will
result).
1k
Ω
Minimum input impedance
Terminate analog output signal
wire directly on J12 daughter
board connector J1.
Analog Output (J12) Daughter
Card Jumper Positions
Jumper
Number
Placement
(4-20mA)
Placement
(0-10V)
JMP1
Pins 2 & 4
Pins 1 & 2
500
Ω
Maximum input imped-
ance
Terminate analog output signal
wire directly on J12 daughter
board connector J1.
NOTE: Voltage signal is self-generated by temp controller, but is not ground-isolated. Customer’s interface must be
isolated from ground (or ground loop damage will result).
NOTE: Current signal is self-generated by temp controller but is not ground-isolated. Customer’s interface must be
isolated from ground (or ground loop damage will result).
NOTE: Both analog input and output signals are not isolated from each other in controller. Customer’s interface must
have isolated channels (or reference loop damage will result).
(Continued)
(continued)
Summary of Contents for Thermolator TW-P
Page 6: ...iv I Table of Contents ...
Page 12: ...1 6 I Introduction ...
Page 36: ...3 14 I ...
Page 58: ...4 22 I Operation ...
Page 72: ...5 14 I Maintenance ...
Page 128: ...E 4 I Appendix ...
Page 134: ...G 4 I Appendix ...
Page 136: ...H 2 I Appendix ...