Operation
I
4-15
4
Opera
tion
Program Menu Items
Item Name
Item
Code
Default
Valve
Range
Alarm delay for high deviation alarm
AdH
30
0 to 60 minutes (10 to 60 minutes on program
versions prior to version 1.33)
Alarm delay for low deviation alarm
AdL
30
0 to 60 minutes (10 to 60 minutes on program
versions prior to version 1.33)
Alarm deviation alarm delay after start
ADS
30
0 to 30 minutes on program version 1.33 and later
only
Alarm output
AdO
DIS
Disabled (DIS) or Enabled (EnA) on program
versions 1.33 and later only
Autostart enable
ASE
ENA
Disabled (DIS) or Enabled (EnA)
Brownout monitor
brn
EnA
Disabled (DIS) or Enabled (EnA)
Communications Baud rate
1
bAU
96
12 to 96
Communications Modbus ID
1
bId
1
1 to 247
Communications SPI address
1
SPA
32
32 to 63
Communications type
1
COt
OFF
OFF, Retransmit (rEt), SPI (SPI), ModBus (bUS),
Handheld Remote (Han)
Crash Cool enabled
1
CCE
DIS
Disabled (DIS) or Enabled (EnA)
Derivative time
dEr
5
0 to 200
Display units
Unt
F
F or C
High deviation alarm limit
HId
10
5 to 100 degrees above set point
Integral time
Int
25
1 to 800
Low deviation alarm limit
Lod
10
5 to 100 degrees below set point
Low pressure bypass enabled
pbE
dIS
Disabled (DIS) or Enabled (EnA)
Panel Temperature Alarm
PAe
EnA
Disabled (DIS) or Enabled (EnA)
Panel Temperature Readout
Pte
Display only
Proportional band
bnd
20
1 to 300
Proportional band ratio
Pbr
5
1 to 10
Pump run hours
PrH
0
0 to 999 (x100)
Purge enabled (optional)
1
PuE
DIS
Disabled (DIS) or Enabled (EnA)
Remote heat/cool enabled
1
rHC
DIS
Disabled (DIS) or Enabled (EnA)
Remote Setpoint enabled
1
rSE
DIS
Disabled (DIS) or Enabled (EnA)
Remote Setpoint high limit
1
rSH
260
rSL to 999
Remote Setpoint low limit
1
rSL
10
-99 to rSH
Retransmit high limit
1
rEH
260
rEL to 999
Retransmit low limit
1
rEL
10
-99 to rEH
Return Temperature Probe Enable
SSE
EnA
Disabled (DIS) or Enabled (EnA)
Seal-Saver enabled
SSE
EnA
Disabled (DIS) or Enabled (EnA)
User high safety limit alarm
HSU
260
Between factory low and high limits
User low safety limit alarm
LSU
22
Between factory low and high limits
User password
UPA
000
0 to 999
Vent sequence cancel temperature
SCt
120
Between factory low and high limits
1
Requires the Premium Controller option (TW-P) as well as the individual option for this function.