Installing UAPs
Unpack and Inspect the Quick Release Ceiling Mount Kit
1
Inspect the exterior of the shipping container(s) for evidence of rough handling that may have damaged
the components in the container.
2
Unpack each container while carefully checking the contents for damage and verify with the packing slip.
Overview of Using a Quick Release Ceiling Mount Kit
The UAP Quick Release Ceiling Mount kit is designed to be installed in a standard 60 cm x 60 cm (2' x 2')
suspended ceiling grid. If the grid uses 120 cm x 60 cm (4' x 2') ceiling tiles, add an additional cross-runner
(cross-tee) to the main runner to support the unit. A minimum overhead clearance of 70 cm is recommended,
as shown below.
Table 6-3.
Quick Release Ceiling Mount Kit (PN
???????
-00)
Quantity Component
Description
Quantity Component
Description
1
Template
1 each
Left and Right UAP Recess Bar
1 each
UAP Recess Shroud with Mounting
Bracket
4
Guide Lock Pins
It is the responsibility of the installer to ensure that the UAP is safely installed.
Recommended
overhead clearance
is 70 cm (27.6 in)