InteliLite Global Guide
89
Record structure
Name
Abbreviation
Description
Number
No.
Row number (0 corresponds to the last record, -1 to the previous
one, etc.)
Reason
Reason
Reason for history record (any event or alarm related to the gen-set
Time
Time
Time
Date
Date
Date
RPM
RPM
Engine rotations per minute
Power
Pwr
Generator active power
Reactive power
Q
Generator reactive power
Power Factor
PF
Generator power factor
Load Character
LChr
Generator load character
Generator
Frequency
Gfrq
Generator Frequency
Generator Voltage
Vg1
Generator voltage Ph1
Generator Voltage
Vg2
Generator voltage Ph2
Generator Voltage
Vg3
Generator voltage Ph3
Generator Voltage
Vg12
Generator voltage Ph12
Generator Voltage
Vg23
Generator voltage Ph23
Generator Voltage
Vg31
Generator voltage Ph31
Generator Current
Ig1
Generator current Ph1
Generator Current
Ig2
Generator current Ph2
Generator Current
Ig3
Generator current Ph3
Voltage Battery
VBat
Voltage of battery
Analog Input 1
Ain1
Analog input 1
Analog Input 2
Ain2
Analog input 2
Analog Input 3
Ain3
Analog input 3
Analog Input 4
Ain4
Analog input 4
Binary Inputs
BIN
Controller binary inputs
Binary Outputs
BOUT
Controller binary outputs
Controller Mode
Mode
Controller mode
Note:
When some setpoint is changed, in history log is written its number of communication object.
5.4.10 Breaker control
The following power switches are controlled by the controller:
The generator circuit breaker or contactor – GCB
It is possible to use either a motorized circuit breaker or contactor. Below is a list of available control outputs
that should fit all types of contactors or breakers. The following rules must be kept to when designing the wiring
of power switches:
Summary of Contents for InteliLite MRS16
Page 40: ...InteliLite Global Guide 40 4 4 12 Example of MRS Wiring ...
Page 55: ...InteliLite Global Guide 55 ...
Page 56: ...InteliLite Global Guide 56 ...
Page 57: ...InteliLite Global Guide 57 ...
Page 58: ...InteliLite Global Guide 58 ...
Page 59: ...InteliLite Global Guide 59 ...
Page 60: ...InteliLite Global Guide 60 Setpoint Screens ...
Page 61: ...InteliLite Global Guide 61 History Log ...
Page 62: ...InteliLite Global Guide 62 ...
Page 63: ...InteliLite Global Guide 63 ...
Page 64: ...InteliLite Global Guide 64 ...
Page 65: ...InteliLite Global Guide 65 5 3 3 Browsing alarms ...
Page 66: ...InteliLite Global Guide 66 5 3 4 Password Enter password ...
Page 67: ...InteliLite Global Guide 67 Change password ...
Page 68: ...InteliLite Global Guide 68 Note Use Up and Down button to select required level of password ...
Page 69: ...InteliLite Global Guide 69 Log out from controller ...
Page 71: ...InteliLite Global Guide 71 5 3 6 Language selection ...
Page 72: ...InteliLite Global Guide 72 ...
Page 78: ...InteliLite Global Guide 78 Image 5 13 Flowchart of start of diesel engine ...
Page 80: ...InteliLite Global Guide 80 Image 5 14 Flowchart of start of gas engine ...
Page 582: ...InteliLite Global Guide 582 more information see Alarm types Level 2 on page 84 ...