InteliLite Global Guide
23
4.4.1 General
To ensure proper function:
Use grounding terminals.
Wiring for binary inputs and analog inputs must not be run with power cables.
Analog and binary inputs should use shielded cables, especially when the length is more than 3 m.
Tightening torque, allowable wire size and type, for the Field-Wiring Terminals:
For Mains(Bus) Voltage, Generator Voltage and Current terminals
Specified tightening torque is 0,56 Nm (5,0 In-lb)
use only diameter 2,0 - 0,5 mm (12 - 26 AWG) conductor,
rated for 90°C minimum.
For other controller field wiring terminals
Specified tightening torque 0,79 nm (7,0 In-lb)
Use only diameter 2,0 - 0,5 mm (12 - 26 AWWG) conductor,
rated for 75°C minimum.
use copper conductors only
4.4.2 Grounding
The shortest possible piece of wire should be used for controller grounding. Use cable min 2,5 mm2.
The negative " - " battery terminal must be properly grounded.
Switchboard and engine must be grounded at common point. Use as short cable as possible to the grounding
point.
4.4.3 Power supply
To ensure proper function:
Use power supply cable min. 1,5 mm2
Maximum continuous DC power supply voltage is 36 VDC. The controller’s power supply terminals are
protected against large pulse power disturbances. When there is a potential risk of the controller being subjected
to conditions outside its capabilities, an outside protection device should be used.
Summary of Contents for InteliLite MRS16
Page 40: ...InteliLite Global Guide 40 4 4 12 Example of MRS Wiring ...
Page 55: ...InteliLite Global Guide 55 ...
Page 56: ...InteliLite Global Guide 56 ...
Page 57: ...InteliLite Global Guide 57 ...
Page 58: ...InteliLite Global Guide 58 ...
Page 59: ...InteliLite Global Guide 59 ...
Page 60: ...InteliLite Global Guide 60 Setpoint Screens ...
Page 61: ...InteliLite Global Guide 61 History Log ...
Page 62: ...InteliLite Global Guide 62 ...
Page 63: ...InteliLite Global Guide 63 ...
Page 64: ...InteliLite Global Guide 64 ...
Page 65: ...InteliLite Global Guide 65 5 3 3 Browsing alarms ...
Page 66: ...InteliLite Global Guide 66 5 3 4 Password Enter password ...
Page 67: ...InteliLite Global Guide 67 Change password ...
Page 68: ...InteliLite Global Guide 68 Note Use Up and Down button to select required level of password ...
Page 69: ...InteliLite Global Guide 69 Log out from controller ...
Page 71: ...InteliLite Global Guide 71 5 3 6 Language selection ...
Page 72: ...InteliLite Global Guide 72 ...
Page 78: ...InteliLite Global Guide 78 Image 5 13 Flowchart of start of diesel engine ...
Page 80: ...InteliLite Global Guide 80 Image 5 14 Flowchart of start of gas engine ...
Page 582: ...InteliLite Global Guide 582 more information see Alarm types Level 2 on page 84 ...