InteliLite Global Guide
584
Shutdown
Alarm Type
Shutdown
Alarmlist message
Emergency Stop
Alarm evaluated
All the time
Related applications
AMF, MRS
Description
Alarm is activated when binary input
is activated.
The gen-set shuts down in the moment the input is activated and starting is
blocked until the input is deactivated and fault reset is pressed.
Note:
Use red emergency button placed on the switchboard door and connect
it to a binary input of the controller. Then configure the function Emergency
Stop to this binary input. It is recommended to use NC contact of the button.
Note:
The MCB control is not affected by this alarm.
Emergency Stop
back to List of alarms level 2
Alarm Type
Shutdown
Alarmlist message
Sd Battery Flat
Alarm evaluated
During cranking
Related applications
AMF, MRS
Description
This alarm will be issued if the controller was reset during cranking of the gen-set.
If this situation occurs, the controller supposes the starting battery is so exhausted
that its voltage drops so low when starter motor is energized that it causes
controller reset.
Sd Battery Flat
back to List of alarms level 2
Alarm Type
Shutdown
Alarmlist message
Sd Coolant Temp
Alarm evaluated
All the time
Related applications
AMF, MRS
Description
This alarm indicates that the coolant temperature is higher than the temperature set
in
Coolant Temperature Sd (page 179)
setpoint.
Sd Coolant Temp
back to List of alarms level 2
Alarm Type
Shutdown
Alarmlist message
Sd Current Unbalance
Alarm evaluated
All the time
Sd Current Unbalance
Summary of Contents for InteliLite MRS16
Page 40: ...InteliLite Global Guide 40 4 4 12 Example of MRS Wiring ...
Page 55: ...InteliLite Global Guide 55 ...
Page 56: ...InteliLite Global Guide 56 ...
Page 57: ...InteliLite Global Guide 57 ...
Page 58: ...InteliLite Global Guide 58 ...
Page 59: ...InteliLite Global Guide 59 ...
Page 60: ...InteliLite Global Guide 60 Setpoint Screens ...
Page 61: ...InteliLite Global Guide 61 History Log ...
Page 62: ...InteliLite Global Guide 62 ...
Page 63: ...InteliLite Global Guide 63 ...
Page 64: ...InteliLite Global Guide 64 ...
Page 65: ...InteliLite Global Guide 65 5 3 3 Browsing alarms ...
Page 66: ...InteliLite Global Guide 66 5 3 4 Password Enter password ...
Page 67: ...InteliLite Global Guide 67 Change password ...
Page 68: ...InteliLite Global Guide 68 Note Use Up and Down button to select required level of password ...
Page 69: ...InteliLite Global Guide 69 Log out from controller ...
Page 71: ...InteliLite Global Guide 71 5 3 6 Language selection ...
Page 72: ...InteliLite Global Guide 72 ...
Page 78: ...InteliLite Global Guide 78 Image 5 13 Flowchart of start of diesel engine ...
Page 80: ...InteliLite Global Guide 80 Image 5 14 Flowchart of start of gas engine ...
Page 582: ...InteliLite Global Guide 582 more information see Alarm types Level 2 on page 84 ...