InteliLite Global Guide
137
Register
addresses
Number of
registers
Access
Data type
Meaning
4566 - 4592
27
read
Alarm
14. record in alarm list
4593 - 4619
27
read
Alarm
15. record in alarm list
4620 - 4646
27
read
Alarm
16. record in alarm list
List of commands and arguments
"Commands" are used to invoke a specific action in the controller via the communication channel. The list of
available actions is in the table below. The general procedure of writing a command via MODBUS is as follows:
1. (Optional) Write required level of password into the register 44212 (register address 4211). Use function 6. If
the password is required or not depends on configuration of access rules. It can be adjusted/modified by
LiteEdit2015.
2. Write the command argument into the registers 44208-44209 (register addresses 4207-4208). Use function
16.
3. Write the command code into the register 44210 (register address 4209). Use function 6.
4. (Optional) Read the command return value from the registers 44208-44209 (register addresses 4207-4208).
Use function 3.
5. If the command was executed the return value is as listed in the table. If the command was accepted but
there was an error during execution the return value indicates the reason:
a. 0x00000001 – invalid argument
b. 0x00000002 – command refused (e.g. controller not in MAN, breaker can not be closed in the specific
situation etc.)
Action
Command code
Argument
Return value
Engine start *)
0x01
0x01FE0000
0x000001FF
Engine stop *)
0x01
0x02FD0000
0x000002FE
Fault reset *)
0x01
0x08F70000
0x000008F8
Horn reset *)
0x01
0x04FB0000
0x000004FC
GCB toggle *)
0x02
0x11EE0000
0x000011EF
GCB on
0x02
0x11EF0000
0x000011F0
GCB off
0x02
0x11F00000
0x000011F1
MCB toggle *)
0x02
0x12ED0000
0x000012EE
MCB on
0x02
0x12EE0000
0x000012EF
MCB off
0x02
0x12EF0000
0x000012F0
*) This action is an equivalent of pressing the front panel button
Summary of Contents for InteliLite MRS16
Page 40: ...InteliLite Global Guide 40 4 4 12 Example of MRS Wiring ...
Page 55: ...InteliLite Global Guide 55 ...
Page 56: ...InteliLite Global Guide 56 ...
Page 57: ...InteliLite Global Guide 57 ...
Page 58: ...InteliLite Global Guide 58 ...
Page 59: ...InteliLite Global Guide 59 ...
Page 60: ...InteliLite Global Guide 60 Setpoint Screens ...
Page 61: ...InteliLite Global Guide 61 History Log ...
Page 62: ...InteliLite Global Guide 62 ...
Page 63: ...InteliLite Global Guide 63 ...
Page 64: ...InteliLite Global Guide 64 ...
Page 65: ...InteliLite Global Guide 65 5 3 3 Browsing alarms ...
Page 66: ...InteliLite Global Guide 66 5 3 4 Password Enter password ...
Page 67: ...InteliLite Global Guide 67 Change password ...
Page 68: ...InteliLite Global Guide 68 Note Use Up and Down button to select required level of password ...
Page 69: ...InteliLite Global Guide 69 Log out from controller ...
Page 71: ...InteliLite Global Guide 71 5 3 6 Language selection ...
Page 72: ...InteliLite Global Guide 72 ...
Page 78: ...InteliLite Global Guide 78 Image 5 13 Flowchart of start of diesel engine ...
Page 80: ...InteliLite Global Guide 80 Image 5 14 Flowchart of start of gas engine ...
Page 582: ...InteliLite Global Guide 582 more information see Alarm types Level 2 on page 84 ...