Installation Guide_PV-ezRack_SolarTerraceIII-A_AU_V2.0
1/10 Duerdin Street, Clayton VIC 3168 Australia
Tel: +61 3 9239 8088 Fax: +61 3 9239 8024
E-mail: [email protected] www.clenergy.com.au
06
page
of 28
Notes
:
• The footing example shown are recommended for “firm” soils with allowable endbearing
capacity of 100 kPa minimum (damp clays, sandy clays, damp sands). Contact Clenergy
for site specific conditions (to find out whetheramore cost effective solutionis possible);
• Concrete grade: N25 minimum, cover: 50 mm (contact Clenergy to find out whether a
more cost effective solution is possible, based on site specific conditions);
• For fixing the STIII-A support to the concrete footing, we recommend using M16(5.8
grade Carbon Steel anchor studs or similar). Adopt the minimum anchor embedment
depth designated by the anchors manufacturer’s manual. Clenergy STIII-A has 6 anchors
per frame, 2 at the front and 4 at the rear;
• Rail end overhang should be not over 40% of the support spacing.
• Other footing options are possible – contact Clenergy.
Planning
Individual Pad Footings per Leg
Transverse Strip Footing